Common questions
Common Questions
20 totalWhat is the factory default setting on the UPS3 15-50/65?
The pump is factory set to constant curve III. At speed III, the pump runs at a constant speed on the maximum curve under all operating conditions. Quick venting of the pump can also be obtained by setting the pump to speed III for a short period. (Page 7, 11, 15)
How do I vent the pump after installation?
Set the pump to speed III using the button on the operating panel, then let the pump run for a minimum of 30 minutes. How fast the pump is vented depends on the system size and design. Small air pockets may cause noise initially, but because the pump is self-venting through the system, the noise will cease over time. (Page 7)
What does a red LED on the operating panel mean?
If the pump has detected one or more alarms or warnings, the first LED switches from green to red. When the fault has been resolved, the operating panel switches back to operating status and the LED returns to green. If multiple alarms are active simultaneously, the LEDs only show the error with the highest priority. (Page 11, 17)
How do I fix a blocked pump on the UPS3 15-50/65?
Switch off the power supply, close the valves, then locate the deblocking screw in the centre of the control box and use a size 2 Phillips tip star screwdriver to push the screw inwards. When the screw can be turned counterclockwise, the shaft has been deblocked — repeat if necessary, then switch the power supply back on. The pump deblocking device is accessible from the front without having to demount the control box. (Page 17)
What are the three alarm/warning types and their solutions?
There are three fault conditions: a blocked pump alarm (pump stops) requires deblocking the shaft per section 9.1; a low supply voltage warning (pump keeps running) requires ensuring sufficient voltage supply; and an electrical error alarm (pump stops) requires replacing the pump and returning it to your supplier. (Page 17)
How do I change the control mode between constant curve and proportional/constant pressure?
Press the button on the operating panel to cycle through constant curve settings I, II, and III. To select a proportional-pressure or constant-pressure curve, press and hold the button for 3 seconds; press and hold again for 3 seconds to return to constant-curve settings. The LEDs will indicate the chosen control mode. (Page 15)
Show 14 more questions
What are the liquid temperature and pressure limits for the UPS3 15-50/65?
What pump positions are allowed during installation?
How do I connect an external PWM control signal to the UPS3?
What should I do if my UPS3 pump is blocked?
How do I identify an alarm on my UPS3 pump?
How do I set the PWM input signal for my UPS3 pump?
What are the recommended control modes for different heating system types?
What safety precautions must be taken before performing any work on the pump?
How do I start up and vent the UPS3 pump?
What happens if there is low voltage detected by the UPS3 pump?
How do I dismantle the UPS3 pump for servicing?
What is the factory default setting for UPS3 control modes?
How do I install the UPS3 pump?
Can I use insulation on my UPS3 pump housing?
Full Manual
22 pages
English (GB) 2 English (GB) Installation and operating instructions Original installation and operating instructions These installation and operating instructions describe Grundfos
Ups3.
Sections 1-4 give the information necessary to be able to unpack, install and start up the product in a safe way. Sections 5-12 give important information about the product, as well as information on service, fault finding and disposal of the product.Contents
PageDanger
Indicates a hazardous situation which, if not avoided, will result in death or serious personal injury.Warning
Indicates a hazardous situation which, if not avoided, could result in death or serious personal injury.Caution
Indicates a hazardous situation which, if not avoided, could result in minor or moderate personal injury.Signal Word
Description of hazard Consequence of ignoring the warning.English (GB) 3 1.2 Notes The symbols and notes below may appear in Grundfos installation and operating instructions, safety instructions and service instructions.
Caution
Crushing of feet Minor or moderate personal injuryDanger
Electric shock Death or serious personal injuryCaution
Crushing of feet Minor or moderate personal injuryTm07 0368 1518
Tm07 0369 1518
English (GB) 4 Fig. 3 Tightening the fittings 3.2 Pump positions Always install the pump with a horizontal motor shaft within ± 5 °. Do not install the pump with a vertical motor shaft. See fig. 4, bottom row. • Pump installed correctly in a vertical pipe. See fig. 4, top row, left. • Pump installed correctly in a horizontal pipe. See fig. 4, top row, right. Fig. 4 Pump positions 3.3 Control box positions The control box can be mounted in all positions. See fig. 5. Fig. 5 Possible control box positions
Tm07 0370 1518
Tm07 0371 1518
Danger
Electric shock Death or serious personal injuryCaution
Hot surface Minor or moderate personal injuryCaution
Pressurised system Minor or moderate personal injuryTm06 7297 0918
English (GB) 5 3.3.1 Changing the control box position 3.4 Electrical connection • The motor requires no external motor protection. • Check that the supply voltage and frequency correspond to the values stated on the nameplate. See section 5.4.1 Nameplate. • Connect the pump to the power supply with the plug supplied with the pump. See steps 1 to 7. 3.5 Assembling the installer plug Step Action Illustration 1 Make sure that the inlet and outlet valves are closed. Unscrew the screws on the pump head.
Tm07 0372 1518
2 Turn the pump head to the desired position.Tm07 0373 1518
3 Refit the screws on the pump head.Tm07 0374 1518
Danger
Electric shock Death or serious personal injuryDanger
Electric shock Death or serious personal injuryDanger
Electric shock Death or serious personal injuryDanger
Electric shock Death or serious personal injuryTm06 8542 0918
2 Detach the terminal cover.Tm06 8543 0918
3 Pull the power cable through the cable gland and terminal cover.Tm06 8544 0918
4 Strip the cable conductors as illustrated.Tm06 8545 0918
5 Loosen the screws on the power supply plug and connect the cable conductors.Tm06 8546 0918 - Tm06 8547 0918
6 Tighten the screws on the power supply plug.Tm06 8548 0918
0/Off 1/On 42 mm 32 mm Ø 5.5 - 10 mm 0.5 - 1.5 mm2 8 mmL
Pe
N
x 3 x 3English (GB) 6 3.6 Insulating the pump housing Fig. 6 Insulating the pump housing You can reduce the heat loss from the pump and pipe by insulating the pump housing and the pipe with insulating shells, which can be ordered as an accessory. See section 5.5.2 Insulating shells. 7 Refit the terminal cover. See A. Note: It is possible to turn the power supply plug on the side for a 90 ° cable entry. See B.
Tm06 8549 0918 - Tm06 8550 0918
8 Tighten the union nut.Tm06 8551 0918
9 Tighten the cable gland onto the power supply plug.Tm06 8552 0918
10 Insert the power supply plug into the male plug on the pump.Tm07 0376 1518
Step Action IllustrationB
A
Tm07 0375 1518
Do not insulate the control box or cover the operating panel.English (GB) 7
Tm07 0377 1518
2 Switch on the power supply.Tm06 8555 1317
3 The lights in the operating panel indicates that the power supply has been switched on and the pump is running.Tm07 0378 1518
0/Off 1/OnTm07 1416 1618
The pump must not run dry. The pump is from factory set to constant curve III. Hold 3 sec. Minimum 30 min.English (GB) 8
Caution
Flammable material Minor or moderate personal injuryCaution
Corrosive substance Minor or moderate personal injuryTm07 0791 1618
Pos. Description 1 Pump name 2 Minimum current [A] 3 Maximum current [A] 4 CE mark and approvals 5 Energy Efficiency Index, EEI 6 Voltage [V] 7 Average power input PL, avg (Ecodesign regulation) 8 Model designation 9 Product number 10 Serial number 11 Country of origin 12 Frequency [Hz] 13 Part, according to EEI 14 Enclosure class 15 Manufacturer’s name and address 16 Production code:X.Xx
X.Xx
Xx
Xxx
X.X
((,0.XX - Part X XXXV ~ XX/XXHz IPXXX TFXXXP/N:Xxxxxxxx
S/N:Xxxxxxxx
Made in XXXXXXX PL.avg.Ups3
Hold 3 sec.Pc:P1Xxxx
English (GB) 9 5.4.2 Type key 5.5 Accessories 5.5.1 Unions and valve kits Note: The product numbers are always for one complete set, including gaskets. The product number for the standard sizes is printed in bold. G-threads have a cylindrical form in accordance with the EN ISO 228-1 standard and are not sealing the thread. It requires a flat gasket. You can only screw male G-threads (cylindrical) into female G-threads. The G-threads are standard thread on the pump housing. R-threads are tapered external threads in accordance with the EN 10226-1 standard. Rc- or Rp-threads are internal threads with either tapered or cylindrical (parallel) threads. You can screw male R-threads (conical) into female Rc- or Rp-threads. See fig. 9. Fig. 9 G-threads and R-threads 5.5.2 Insulating shells The accessory set is tailored to the individual pump type. The insulating shells enclose the entire pump housing and are easy to fit around the pump. Example
Ups3
15 50/65 130 Pump type Nominal diameter (DN) of inlet and outlet ports [mm] Maximum head [dm] [ ]: Cast-iron pump housing Port-to-port length [mm] Product numbers, unions Union nut with internal threads Union nut with external threadsUps3
Connection 3/4 1 1 1/4 1 1 1/4 15-xxG 1
1/2 529921 529922 529821 529925 529924Tm07 7425
Pump type Product numberUps3 15-50/65
99270706 RpR
R
RpG
English (GB) 10 5.5.3 Cables and plugs The pump has two electrical connections: the power supply and the control signal connection. Power supply connection The installer plug is supplied with the pump and is available as an accessory. Power cable adapters are also available as accessories. Control signal connection The control signal cable connection has three conductors: the signal input, the signal output and the signal reference. Connect the cable to the control box by a mini superseal plug. See 7.1 Setting the PWM input signal. The optional signal cable is available as an accessory. The cable length must not exceed 3 metres. Fig. 10 Mini superseal plug
Tm06 4414
Conductor Colour Signal input Brown Signal reference Blue Signal output Black Product Product description Length [mm] Product number Installer plug 99439948 Mini superseal signal cable (PWM input signal) 2000 99165309 Superseal power cable 2000 99198990 Power cable adapter: Superseal Molex cable adapter, overmoulded 150 99165311 Power cable adapter: Superseal Volex cable adapter, overmoulded 150 99165312English (GB) 11
Tm07 1516 1618
Symbol Description ButtonI, Ii, Iii
Constant curve or constant speed curve I, II andIii
Proportional-pressure mode I, II Constant-pressure mode, I, IITm06 8822 1217
Ups3
Hold 3 sec.Q
H
The pump is factory-set to constant curve III. System type Recommended control mode Alternative control mode One-pipe heating system Constant-pressure mode. See section 6.2.3 Constant pressure I, II. Constant curve or constant speed, I, II or III.Tm07 1552 1618
System type Recommended control mode Alternative control mode Two-pipe system Proportional- pressure mode* Constant curve or constant speed I, II, III, see section 6.2.1 Constant curve or constant speed, I, II or III (factory setting).Tm07 1553 1618
System type Recommended control mode Alternative control mode Underfloor heating system Constant-pressure mode Constant curve or constant speed I, II, III, see section 6.2.1 Constant curve or constant speed, I, II or III (factory setting).Q
H
I
Ii
Q
H
I
Ii
English (GB) 12 6.2.4 Changing from recommended to alternative pump setting Heating systems are relatively slow systems that cannot be set to the optimum operation within minutes or hours. If the recommended pump setting does not give the desired distribution of heat in the rooms of the house, change the pump setting to the shown alternative. 6.2.5 Selecting the control modes Proportional pressure We recommend proportional-pressure mode in variable flow systems with relatively large pressure losses in the distribution pipes such as: • two-pipe heating systems with thermostatic valves and long distribution pipes • two-pipe heating systems with thermostatic valves and high pressure losses in system parts with total flow • primary circuit pumps in systems with large pressure losses in the primary circuit. Note: Proportional-pressure mode is not recommended in heating systems that includes an automatic bypass valve to ensure a minimum flow for the heating appliances. Constant pressure We recommend constant-pressure mode in variable flow systems with relatively small pressure losses in the distribution pipes such as: • two-pipe heating systems with thermostatic valves and dimensioned for natural circulation (former gravity systems) • two-pipe heating systems with thermostatic valves and low pressure losses in system parts with total flow • one-pipe heating systems with thermostatic valves or pipe balancing valves • underfloor heating systems with zone valves • primary circuit pumps in systems with small pressure losses in the primary circuit. Constant curve We recommend constant-curve mode in constant-flow systems, where both a constant flow rate and a constant head are required, such as: • heat surfaces • replacement for uncontrolled circulator pumps, for instance integrated in boilers. 6.3 Control signal The pump can be controlled via a digital low-voltage pulse-width modulation (PWM) signal. The square-wave PWM signal is designed for a 100 to 4,000 Hz frequency range. The PWM signal is used to select the speed (speed command) and as feedback signal. The PWM frequency on the feedback signal is fixed at 75 Hz in the circulator pump. For instructions on how to set the connection, see section 7.1 Setting the PWM input signal. Duty cycle d % = 100 x t/T Example Fig. 15 PWM signal 6.3.1 Interface The pump’s interface consists of an electronic part connecting the external control signal to the circulator pump. The interface translates the external signal into a signal type that the microprocessor can understand. In addition, the interface ensures that the user cannot get into contact with dangerous voltage if touching the signal wires when power is connected to the circulator pump. Note: "Signal ref." is a signal reference with no connection to protective earth. Fig. 16 Schematic drawing, interface Example Rating T = 2 ms (500 Hz) UiH = 4-24 V t = 0.6 ms UiL ≤ 1 V d % = 100 x 0.6 / 2 = 30 % IiH ≤ 10 mA (depending on UiH)
Tm04 9911 0211
Abbreviation DescriptionT
Period of time [sec.] d Duty cycle [t/T] UiH High-level input voltage UiL Low-level input voltage IiH High-level input currentTm06 0787 0914
T
t UiH UiL 5 9S
5 %&% %&% 7/3 7/3N
N
+English (GB) 13 6.3.2 PWM input signal profile A (heating) The pump runs on constant-speed curves depending on the PWM input signal. The speed decreases when the PWM value increases. If the PWM signal equals zero (0 VDC), the pump will switch to the control mode selected before connecting to a PWM signal. Fig. 17 PWM input signal profile A (heating) 6.3.3 PWM feedback signal The PWM feedback signal offers pump information like in bus systems: • current power consumption (accuracy ± 2 % of PWM signal) • warning • alarm. Alarms Alarm output signals are available because some PWM output signals are dedicated to alarm information. If a supply voltage is measured below the specified supply voltage range, the output signal is set to 75 %. If the rotor is locked due to deposits in the hydraulics, the output signal is set to 90 % because this alarm has a higher priority. See fig. 18. Fig. 18 PWM feedback signal - power consumption Data
Tm06 9136 1617
PWM input signal [%] Pump status ≤ 10 Maximum speed: max. > 10 / ≤ 84 Variable speed: min. to max. > 84 / ≤ 91 Minimum speed: IN > 91/95 Hysteresis area: on/off > 95 or ≤ 100 Standby mode: off PWM input signal [%] Max. Speed PWM input signal Max. SpeedTm07 1313 1118
Maximum rating Symbol Value PWM frequency input with high-speed optocoupler f 100-4000 Hz Guaranteed standby power consumption< 1 W
Rated input voltage - high level UiH4-24 V
Rated input voltage - low level UiL< 1 V
High-level input current IiH < 10 mA Input duty cyclePwm
0-100 % PWM frequency output, open collector f 75 Hz ± 5 % Accuracy of output signal regarding power consumptionPwm
0-100 % Collector emitter breakdown voltage on output transistor Uc< 70 V
Collector current on output transistor Ic < 50 mA Maximum power dissipation on output resistorPr
125 mW Zener diode working voltage Uz36 V
Maximum power dissipation in Zener diode Pz 300 mW 25 50 100 150 200 250 10 20 30 40 50 60 70 80 90 100 Power [W] Standby (stop) Alarm stop: fault, blocked pump Alarm stop: electrical fault Warning Saturation at 70 Watt Slope: 1 W / % PWMEnglish (GB) 14 6.4 Pump performance Figure 19 shows the relation between pump setting and pump performance by means of curves. Fig. 19 Pump setting in relation to pump performance
Tm07 1541 1618
Q
H
Setting Pump curve FunctionI
Constant curve or constant speed I The pump runs at a constant speed and consequently on a constant curve. At speed I, the pump is set to run on the minimum curve under all operating conditions.Ii
Constant curve or constant speed II The pump runs at a constant speed and consequently on a constant curve. At speed II, the pump is set to run on the intermediate curve under all operating conditions.Iii
Constant curve or constant speed III (factory setting) The pump runs at a constant speed and consequently on a constant curve. At speed III, the pump is set to run on the maximum curve under all operating conditions. Quick venting of the pump can be obtained by setting the pump to speed III for a short period. Proportional-pressure mode I,Ii
The duty point of the pump will move up or down on a proportional-pressure curve, depending on the heat demand in the system. The head (pressure) is reduced at falling heat demand and increased at rising heat demand. Constant-pressure mode I, II The duty point of the pump will move out or in on a constant-pressure curve, depending on the heat demand in the system. The head (pressure) is kept constant, irrespective of the heat demand.English (GB) 15
Tm064414
Tm07 0379 1518
1 x 230 V - 15 %/+ 10 % ∽ 50/60 Hz 1 x 230 V ∽ 50/60English (GB) 16
Danger
Electric shock Death or serious personal injuryDanger
Electric shock Death or serious personal injuryCaution
Hot surface Minor or moderate personal injuryCaution
Pressurised system Minor or moderate personal injuryEnglish (GB) 17
Danger
Electric shock Death or serious personal injuryCaution
Hot surface Minor or moderate personal injuryCaution
Pressurised system Minor or moderate personal injuryTm07 0387 1518
Before, during and after the deblocking, the device is tight and must not release any water. 2 3 0/Off 1/On 1 No.2 5 mmEnglish (GB) 18
75 °C
0.005 MPa, 0.05 bar, 0.5 m head95 °C
0.05 MPa, 0.5 bar, 5 m head Maximum inlet pressure 1 MPa (10 bar) Ambient temperature0-55 °C
Liquid temperature2-95 °C
Liquid Maximum water/propylene glycol mixture is 50 % Viscosity Maximum 10 mm2/s Maximum altitude of installation 2000 m above sea level Electrical data Supply voltage 1 x 230 V - 15 %/+ 10 %, 50/60 Hz, PE Insulation classF
Standby power consumption< 1 W
Inrush current< 4 A
Minimum switching time power on/off No specific requirements Miscellaneous data Motor protection The pump requires no external motor protection. Enclosure classIpx4D
Temperature class (TF)Tf95
Specific EEI valuesUps3 15-50/65: Eei ≤ 0.20
Tm07 0792 1518
H2
H1
H4
H3
B4
L3
B2
B1
B3
G
L4
L
Ups3
Pump type Dimensions [mm]L
L3
L4
B1
B2
B3
B4
H1
H2
H3
H4
G
Ups3 15-50/65
130 89 45 54 54 64 47 25 102 47 149G 1 1/2
English (GB) 19
Tm07 0800 1318
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 Q [m³/h] 0 1 2 3 4 5 6 [m]H
0 10 20 30 40 50 60 [kPa] p 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Q [l/s] 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 Q [m³/h] 0 10 20 30 40 50 60[W]
P1
SettingP1
[W]
I1
[A]
Min. 4 0.05 Max. 60 0.52English (GB) 20
Grundfos companies Argentina Bombas GRUNDFOS de Argentina S.A. Ruta Panamericana km. 37.500 Centro Industrial Garin 1619 Garín Pcia. de B.A. Phone: +54-3327 414 444 Telefax: +54-3327 45 3190 Australia GRUNDFOS Pumps Pty. Ltd. P.O. Box 2040 Regency Park South Australia 5942 Phone: +61-8-8461-4611 Telefax: +61-8-8340 0155 Austria GRUNDFOS Pumpen Vertrieb Ges.m.b.H. Grundfosstraße 2 A-5082 Grödig/Salzburg Tel.: +43-6246-883-0 Telefax: +43-6246-883-30 Belgium N.V. GRUNDFOS Bellux S.A. Boomsesteenweg 81-83 B-2630 Aartselaar Tél.: +32-3-870 7300 Télécopie: +32-3-870 7301 Belarus Представительство ГРУНДФОС в Минске 220125, Минск ул. Шафарнянская, 11, оф. 56, БЦ «Порт» Тел.: +375 17 397 397 3 +375 17 397 397 4 Факс: +375 17 397 397 1 E-mail: [email protected] Bosnia and Herzegovina GRUNDFOS Sarajevo Zmaja od Bosne 7-7A, BH-71000 Sarajevo Phone: +387 33 592 480 Telefax: +387 33 590 465 www.ba.grundfos.com e-mail: [email protected] Brazil
Bombas Grundfos Do Brasil
Av. Humberto de Alencar Castelo Branco, 630Cep 09850 - 300
São Bernardo do Campo - SP Phone: +55-11 4393 5533 Telefax: +55-11 4343 5015 Bulgaria Grundfos Bulgaria EOOD Slatina District Iztochna Tangenta street no. 100 BG - 1592 Sofia Tel. +359 2 49 22 200 Fax. +359 2 49 22 201 email: [email protected] Canada GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, OntarioL6H 6C9
Phone: +1-905 829 9533 Telefax: +1-905 829 9512 China GRUNDFOS Pumps (Shanghai) Co. Ltd. 10F The Hub, No. 33 Suhong Road Minhang District Shanghai 201106Prc
Phone: +86 21 612 252 22 Telefax: +86 21 612 253 33Colombia
GRUNDFOS Colombia S.A.S. Km 1.5 vía Siberia-Cota Conj. Potrero Chico, Parque Empresarial Arcos de Cota Bod.1A.
Cota, Cundinamarca Phone: +57(1)-2913444 Telefax: +57(1)-8764586 Croatia GRUNDFOS CROATIA d.o.o. Buzinski prilaz 38, Buzin HR-10010 Zagreb Phone: +385 1 6595 400 Telefax: +385 1 6595 499 www.hr.grundfos.com GRUNDFOS Sales Czechia and Slovakia s.r.o. Čajkovského 21 779 00 Olomouc Phone: +420-585-716 111 DenmarkGrundfos Dk A/S
Martin Bachs Vej 3 DK-8850 Bjerringbro Tlf.: +45-87 50 50 50 Telefax: +45-87 50 51 51 E-mail: [email protected] www.grundfos.com/DK Estonia GRUNDFOS Pumps Eesti OÜ Peterburi tee 92G 11415 Tallinn Tel: + 372 606 1690 Fax: + 372 606 1691 Finland OY GRUNDFOS Pumput AB Trukkikuja 1 FI-01360 Vantaa Phone: +358-(0) 207 889 500 France Pompes GRUNDFOS Distribution S.A. Parc d’Activités de Chesnes 57, rue de Malacombe F-38290 St. Quentin Fallavier (Lyon) Tél.: +33-4 74 82 15 15 Télécopie: +33-4 74 94 10 51 GermanyGrundfos Gmbh
Schlüterstr. 33 40699 Erkrath Tel.: +49-(0) 211 929 69-0 Telefax: +49-(0) 211 929 69-3799 e-mail: [email protected] Service in Deutschland: e-mail: [email protected] Greece GRUNDFOS Hellas A.E.B.E. 20th km. Athinon-Markopoulou Av. P.O. Box 71 GR-19002 Peania Phone: +0030-210-66 83 400 Telefax: +0030-210-66 46 273 Hong Kong GRUNDFOS Pumps (Hong Kong) Ltd. Unit 1, Ground floor Siu Wai Industrial Centre 29-33 Wing Hong Street & 68 King Lam Street, Cheung Sha Wan Kowloon Phone: +852-27861706 / 27861741 Telefax: +852-27858664 Hungary GRUNDFOS Hungária Kft. Tópark u. 8 H-2045 Törökbálint, Phone: +36-23 511 110 Telefax: +36-23 511 111 India GRUNDFOS Pumps India Private Limited 118 Old Mahabalipuram Road Thoraipakkam Chennai 600 096 Phone: +91-44 2496 6800 IndonesiaPt. Grundfos Pompa
Graha Intirub Lt. 2 & 3 Jln. Cililitan Besar No.454. Makasar, Jakarta Timur ID-Jakarta 13650 Phone: +62 21-469-51900 Telefax: +62 21-460 6910 / 460 6901 Ireland GRUNDFOS (Ireland) Ltd. Unit A, Merrywell Business Park Ballymount Road Lower Dublin 12 Phone: +353-1-4089 800 Telefax: +353-1-4089 830 Italy GRUNDFOS Pompe Italia S.r.l. Via Gran Sasso 4 I-20060 Truccazzano (Milano) Tel.: +39-02-95838112 Telefax: +39-02-95309290 / 95838461 Japan GRUNDFOS Pumps K.K. 1-2-3, Shin-Miyakoda, Kita-ku, Hamamatsu 431-2103 Japan Phone: +81 53 428 4760 Telefax: +81 53 428 5005 Korea GRUNDFOS Pumps Korea Ltd. 6th Floor, Aju Building 679-5 Yeoksam-dong, Kangnam-ku, 135-916 Seoul, Korea Phone: +82-2-5317 600 Telefax: +82-2-5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60, LV-1035, Rīga, Tālr.: + 371 714 9640, 7 149 641 Fakss: + 371 914 9646 Lithuania GRUNDFOS Pumps UAB Smolensko g. 6 LT-03201 Vilnius Tel: + 370 52 395 430 Fax: + 370 52 395 431 Malaysia GRUNDFOS Pumps Sdn. Bhd. 7 Jalan Peguam U1/25 Glenmarie Industrial Park 40150 Shah Alam Selangor Phone: +60-3-5569 2922 Telefax: +60-3-5569 2866 Mexico Bombas GRUNDFOS de México S.A. deC.V.
Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto Apodaca, N.L. 66600 Phone: +52-81-8144 4000 Telefax: +52-81-8144 4010 Netherlands GRUNDFOS Netherlands Veluwezoom 35 1326 AE Almere Postbus 220151302 Ca Almere
Tel.: +31-88-478 6336 Telefax: +31-88-478 6332 E-mail: [email protected] New Zealand GRUNDFOS Pumps NZ Ltd. 17 Beatrice Tinsley Crescent North Harbour Industrial Estate Albany, Auckland Phone: +64-9-415 3240 Telefax: +64-9-415 3250 Norway GRUNDFOS Pumper A/S Strømsveien 344 Postboks 235, Leirdal N-1011 Oslo Tlf.: +47-22 90 47 00 Telefax: +47-22 32 21 50 Poland GRUNDFOS Pompy Sp. z o.o. ul. Klonowa 23 Baranowo k. Poznania PL-62-081 Przeźmierowo Tel: (+48-61) 650 13 00 Fax: (+48-61) 650 13 50 Portugal Bombas GRUNDFOS Portugal, S.A. Rua Calvet de Magalhães, 241 Apartado 1079 P-2770-153 Paço de Arcos Tel.: +351-21-440 76 00 Telefax: +351-21-440 76 90 Romania Grundfos Pompe România SRL S-PARK BUSINESS CENTER, ClădireaA2,
etaj 2, Str. Tipografilor, Nr. 11-15, Sector 1, Cod 013714, Bucuresti, Romania, Tel: 004 021 2004 100 E-mail: [email protected] www.grundfos.ro Russia ООО Грундфос Россия ул. Школьная, 39-41 Москва, RU-109544, Russia Тел. (+7) 495 564-88-00 (495) 737-30-00 Факс (+7) 495 564 8811 E-mail [email protected] Serbia Grundfos Srbija d.o.o. Omladinskih brigada 90b 11070 Novi Beograd Phone: +381 11 2258 740 Telefax: +381 11 2281 769 www.rs.grundfos.com Singapore GRUNDFOS (Singapore) Pte. Ltd. 25 Jalan Tukang Singapore 619264 Phone: +65-6681 9688 Telefax: +65-6681 9689 Slovakia GRUNDFOS s.r.o. Prievozská 4D821 09 Bratislava
Phona: +421 2 5020 1426 sk.grundfos.com Slovenia GRUNDFOS LJUBLJANA, d.o.o. Leskoškova 9e, 1122 Ljubljana Phone: +386 (0) 1 568 06 10 Telefax: +386 (0)1 568 06 19 E-mail: [email protected] South Africa Grundfos (PTY) Ltd. 16 Lascelles Drive, Meadowbrook Estate 1609 Germiston, Johannesburg Tel.: (+27) 10 248 6000 Fax: (+27) 10 248 6002 E-mail: [email protected] Spain Bombas GRUNDFOS España S.A. Camino de la Fuentecilla, s/n E-28110 Algete (Madrid) Tel.: +34-91-848 8800 Telefax: +34-91-628 0465 SwedenGrundfos Ab
Box 333 (Lunnagårdsgatan 6) 431 24 Mölndal Tel.: +46 31 332 23 000 Telefax: +46 31 331 94 60 Switzerland GRUNDFOS Pumpen AG Bruggacherstrasse 10 CH-8117 Fällanden/ZH Tel.: +41-44-806 8111 Telefax: +41-44-806 8115 Taiwan GRUNDFOS Pumps (Taiwan) Ltd. 7 Floor, 219 Min-Chuan Road Taichung, Taiwan, R.O.C. Phone: +886-4-2305 0868 Telefax: +886-4-2305 0878 Thailand GRUNDFOS (Thailand) Ltd. 92 Chaloem Phrakiat Rama 9 Road, Dokmai, Pravej, Bangkok 10250 Phone: +66-2-725 8999 Telefax: +66-2-725 8998 Turkey GRUNDFOS POMPA San. ve Tic. Ltd. Sti. Gebze Organize Sanayi Bölgesi Ihsan dede Caddesi,U.S.A.
GRUNDFOS Pumps Corporation 9300 Loiret Blvd. Lenexa, Kansas 66219 Phone: +1-913-227-3400 Telefax: +1-913-227-3500 Uzbekistan Grundfos Tashkent, Uzbekistan The Repre- sentative Office of Grundfos Kazakhstan in Uzbekistan 38a, Oybek street, Tashkent Телефон: (+998) 71 150 3290 / 71 150 3291 Факс: (+998) 71 150 3292 Addresses Revised 09.09.202099423997 12.2020