Why is my auxiliary heat running during cooling mode on a heat pump system?

For heat pump systems, auxiliary heat running during cooling is typically caused by a wire incorrectly attached to the W terminal on the UWP. You should verify there is no wire connected to the W terminal, as the manual explicitly states 'Do not use this terminal for heat pump applications.' Refer to the heat pump wiring diagrams to correct the wiring. (Page 13)

From the official Honeywell Honeywell Thermostat Manuals Pro Series Honeywellhome And Others manual, page 13