How do I check that the data being sent between ProBlue P7 melter and controller is correct?

In Sysmac Studio's Watch Tab Page, enter variables such as EIP002_Command_OUT, EIP002_ChannelNumber_OUT etc., set send data for the reading command (EIP002_Command_OUT value of 3), verify that online values update correctly with no faults or alerts reported.