Common questions

Common Questions

10 total
1

What communication protocols does the SEL-2414 support?

The device supports standard protocols including Modbus RTU, DNP3 LAN/WAN, FTP, Telnet, IEC 61850, SEL ASCII, and several others as listed in Chapter 12 of the manual (Page 9).

2

Is there a user interface for troubleshooting on-site?

Yes, the front panel provides visual aids to check field data and calculated values in real-time without needing separate devices. It simplifies commissioning by allowing immediate feedback during setup (Page 7).

3

How do I protect my SEL-2414 Transformer Monitor from environmental hazards?

The device offers robust protection standards such as enclosure ratings and conformal coating for chemically harsh environments or high humidity settings. Always ensure it complies with appropriate UL, cUL, CSA, and CE guidelines (Page 9).

4

How can I reset the SEL-2414 Transformer Monitor to factory defaults?

Press and hold the Power button for 10 seconds until the LED flashes red. This clears all settings and returns the device to factory defaults (Page 23).

5

What I/O options are available for monitoring transformer status?

The SEL-2414 Transformer Monitor includes digital inputs (DI) for measuring critical transformer alarms and status points, such as oil level, pressure, gas accumulation, fans on/off, breakers open/closed, and fault temperature. (Page 3)

6

How do I set up thermal monitoring in the SEL-2414 Transformer Monitor?

Configure the thermal model by selecting ambient and top-oil temperatures or just ambient temperature inputs, based on availability. Temperature data can be received from an RTD/thermocouple card or external modules for precise calculation of hot-spot temperature and insulation aging factors (Page 5).

Show 4 more questions

Full Manual

20 pages
Page 1

SEL-2414 Transformer Monitor

Complete System for Control and Monitoring

![image 1](2414_ds_20180321_images/imageFile1.png)

Major Features and Benefits

The SEL-2414 Transformer Monitor provides an exceptional combination of monitoring, control, and communications in a compact package.

➤ Thermal Monitoring and Metering Capabilities. Safeguard transformers from overheating by tracking thermal conditions. Track the minimum and maximum transformer top oil temperature, hot-spot temperature, and as many as 10 RTDs or thermocouples.

➤ High Reliability, Rugged Design, and Low Price. Apply the SEL-2414 in harsh physical and electrical environments. The SEL-2414 withstands vibration, electrical surges, fast transients, extreme operating temperatures from –40° to +85°C, and meets stringent utility standards. Compare our superior specification compliance, higher reliability, lower price, and worldwide, ten-year warranty to other transformer monitor alternatives.

➤ Flexible I/O for Transformer Status, Alarms, and More. Input/output options include digital inputs for status such as oil level and sudden pressure; RTD and thermocouple inputs for measurements such as ambient, top-oil, and hot-spot temperatures; digital outputs for control and alarms; analog inputs and outputs; and ac current and voltage inputs. Easily program monitoring and control functions with powerful logic, math, timers, counters, and edge-trigger functions. These features allow easy integration with new and retrofit transformer monitor applications. Monitor critical substation assets with comprehensive transformer thermal and through-fault monitoring.

➤ Advanced Asset Monitoring. Monitor critical substation assets with comprehensive transformer thermal and through-fault monitoring. Calculate top oil, hot-spot, insulation aging acceleration factor, and loss of life while generating hourly and daily data about your transformer. Capture the maximum/minimum values of all transformer model quantities. Capture through-fault current data that could lead to increased transformer wear.

➤ Critical Reporting and Logging. Store as many as 512 Sequential Events Recorder (SER) reports of digital input transitions, time-tagged to the nearest millisecond. Analyze SER reports, analog trending, and oscillographic event reports for rapid commissioning, testing, and post-event diagnostics. Send the SER data to a communications processor or computer for system analysis.

➤ Communications and Integration. Automate fan bank control with flexible communication options that provide easy integration with SCADA. Choose from single and dual Ethernet, Modbus® TCP, DNP3 LAN/WAN, IEC 61850, Modbus Serial, EIA-232, EIA-485, Telnet, and File Transfer protocols.

➤ AC Metering Capabilities. The SEL-2414 provides extensive ac metering and monitoring capabilities. Voltage, current, power, energy, power factor, frequency; demand/peak demand metering; and maximum/minimum metering are measured and recorded. Values can be used in programmable calculations and triggers within the meter. ➤ Simple Commissioning Tools. Front-panel HMI provides complete configuration access and displays settings,

measurements, and calculated values. Easily set with ACSELERATOR QuickSet® SEL-5030 Software.

Product Summary

The SEL-2414 Transformer Monitor withstands harsh physical and electrical environments and is built and tested to meet mission-critical IEEE and IEC protective relay standards. Apply the SEL-2414 to satisfy standalone or distributed monitoring and control of transformers, or choose from the flexible communications options to connect to a substation distributed SCADA or automation system, or a SCADA master. Communications options include serial, fiber-optic, and Ethernet connections and ASCII, SEL Fast Message, MIRRORED BITS

® communications, Modbus, and DNP3 protocols. Figure 1 shows the SEL-2414 functionality.

IRIG-B

Up to 10 RTDs or TC (°C)

Up to 12 RTDs

|SEL-2600 RTD Transducer|Communications| |---|---| |SEL-2600 RTD Transducer|Alarms|

Sensor(s) with DOs

Sensor(s) with AOs (mA)

DNP3 Alarms (DOs) Analog Outputs

Currents Voltages

52 = Breaker M = Cooling Fan Motor

Core & Coil

Page 2

52

52

52

M

M

Transformer

Figure 1 Functional Block Diagram

M

52

Status

Control

M

Monitoring and Control Features

Apply flexible I/O options to meet the many needs of new or retrofit transformer installations. The SEL-2414 includes four slots for plug-in I/O cards. Use digital inputs (DI) to monitor critical transformer alarms and status points. Use analog inputs (AI) to measure pressure, oil level, temperatures, tap positions, and process-level signals (e.g., 4–20 mA, 0–1 mA) from transducers. Operate cooling fans, equipment, alarms, or provide indication with relay-contact or solidstate digital outputs (DO) and analog outputs (AO). Measure ac currents and ac voltage to calculate three-phase power, demand, energy, save in oscillographic reports, and for automatic control processes.

IRIG-B

Up to 10 RTDs or thermocouples (°C)

Up to 12 RTDs

|SEL-2600 RTD Transducer|Communications| |---|---| |SEL-2600 RTD Transducer|Alarms|

Sensor(s) with DOs

Sensor(s) with AOs (mA)

DNP3 Alarms (DOs) Analog Outputs

![image 2](2414_ds_20180321_images/imageFile2.png)

Currents Voltages

52 = Breaker M = Cooling Fan Motor

Core & Coil

52 52 52 52

Page 3

Status

Control

MMMM

Transformer

Figure 2 Transformer Monitor and Control System

I/O (Status and Alarms) Use digital inputs to monitor critical alarms such as oil levels, pressures, gas accumulation; they may also be used for status points such as fans on/off and breakers open/closed, as shown in Figure 3.

2 DI (Slot A – Partial)

4 DI (Slot C – Partial)

8 DI (Slot Z)

Oil Level (Tank)

Oil Level (Conservator)

Pressure Relief (Tank)

Fault Pressure (Tank)

Sudden Pressure # Gas Accumulation #

Loss of Auxiliary Power

Oil Flow #1

Oil Flow #2

Heat Detector

Deluge Monitor

Fan/Pump #1 Alarm

Fan/Pump #2 Alarm

Oil Level (OLTC)

= Buchholz

|10 RTD/TC (Slot D)| |---| |Ambient| |Top-Oil (3 for 1)| |Hot-Spot (3)| |OLTC Tank Oil| |Spares|

Page 4

|3 CT / 3 PT (Slot E)| |---| |Load Voltage (3 for 1)| |Load Current (3 for 1)|

|Digital Inputs (DIs)|SEL-2414 Transformer Monitor

Comms (Slot B)|Digital Outputs (DOs)| |---|---|---| |Analog Inputs (AIs)|SEL-2414 Transformer Monitor

Comms (Slot B)| |

Figure 3 Monitoring Inputs and Control Outputs

|3 DO (Slot A – Partial)| |---|

| |4 DO (Slot C – Partial)|4 DO (Slot C – Partial)| |---|---|---| |Fan Bank #1 (On/Off)|Fan Bank #1 (On/Off)| | |Fan Bank #2 (On/Off)|Fan Bank #2 (On/Off)| | |Cooling Lockout (Inhibit)|Cooling Lockout (Inhibit)| | |Spares|Spares| |

|Key| |---| |Core & Coil =| |Fan/Pump Bank =| |On-Load Tap Changer =|

#### Analyze Transformer Sequence-of-Events

Record sequence-of-events related to transformer events or operations with the Sequential Events Recorder (SER) function. With this function, you can analyze assertions and deassertions of digital inputs and outputs; as many as 512 state changes to the millisecond for as many as 96 different digital points. The function also captures when the device powers up and a settings change occurs.

SEL-2414 Date: 04/03/2005 Time: 07:21:19 DEVICE

DATE TIME ELEMENT STATE 17 04/03/2005 06:25:51.120 RB01 Deasserted 16 04/03/2005 06:25:51.125 OUT102 Deasserted 15 04/03/2005 06:26:03.049 RB01 Asserted 14 04/03/2005 06:26:03.053 OUT102 Asserted 13 04/03/2005 06:51:17.748 Device Powered Up 12 04/03/2005 06:51:20.361 OUT101 Asserted 11 04/03/2005 06:51:21.366 OUT101 Deasserted 10 04/03/2005 06:54:10.753 Device Settings Changed 9 04/03/2005 06:54:10.762 FAN BANK #2 OFF Asserted 8 04/03/2005 06:54:11.737 OUT101 Deasserted 7 04/03/2005 07:06:01.739 FAN BANK #2 ON Asserted 6 04/03/2005 07:06:02.744 OUT101 Deasserted 5 04/03/2005 07:06:14.993 Device Settings Changed 4 04/03/2005 07:06:15.002 OUT101 Asserted 3 04/03/2005 07:06:15.977 FAN BANK #1 ON Deasserted 2 04/03/2005 07:13:22.947 OUT101 Asserted 1 04/03/2005 07:13:23.951 OUT101 Deasserted

SER Number

Element or Condition

  • Figure 4 Example SER Report
  • Combine SER data from individual SEL-2414 Transformer Monitors into a system-wide log. Synchronize the system with IRIG-B time code and the report data will align perfectly.

  • Figure 5 Combine SER Data From Multiple SEL-2414 Transformer Monitors for a System-Wide Log and Display
  • ![image 3](2414_ds_20180321_images/imageFile3.png)

    Element State

    Page 5

    SER System Log

    ![image 4](2414_ds_20180321_images/imageFile4.png)

    Computer

    ![image 5](2414_ds_20180321_images/imageFile5.png)

    ![image 6](2414_ds_20180321_images/imageFile6.png)

    ![image 7](2414_ds_20180321_images/imageFile7.png)

    ![image 8](2414_ds_20180321_images/imageFile8.png)

    Figure 6 Example SER Collection Architecture

    #### Analyze Transformer Event Waveforms

    Record analog and digital waveforms at 32 samples/cycle for as many as 64 power system cycles, approximately 1 s. Use the event report to move the oscillographic data to your PC. You can plot your event report data with the SEL-5601 ACSELERATOR Analytic Assistant® Software or with Microsoft® Excel®.

    ![image 9](2414_ds_20180321_images/imageFile9.png)

    Event reports contain ac currents, ac voltages, and digital inputs and outputs. The report automatically adjusts content to the I/O cards you use. Reports are stored in nonvolatile memory to protect your data even if power is lost. Event reports are optimized for recording power disturbances and relating them to your process.

    Figure 7 Example SEL-5601 Waveform Plot

    Set the report to capture either 15 or 64 power system cycles of data around the trigger event. For a 60 Hz system, the event report lengths are 0.25 seconds and 1.07 seconds. For a 50 Hz system, the report lengths are 0.30 seconds and 1.28 seconds.

    #### Trend Transformer Temperatures and Other Analog Inputs

    Record measured ambient, transformer top-oil, transformer hot-spot and other analog data (measured or calculated) for trending with the Analog Signal Profile function. This profile (trending) function can track as many as 32 analog channels. The function records the magnitude and time of acquisition of each analog channel. Use the profile report to move trend records to your PC and quickly plot the data with Microsoft Excel or any other spreadsheet application.

    ![image 10](2414_ds_20180321_images/imageFile10.png)

    =>>CPR "REC_NUM","YEAR","MONTH","DAY","HOUR","MIN","SEC","MSEC","VA_MAG","VB_M AG","VC_M AG","AI301","AI302","AI303","AI304","AI305","AI306","1D7A" 14,2005,9,1,12,10,4,261,2092.127,2099.499,2089.107,-0.001,-0.000,

  • -0.001,-0.001,0.001,-0.001,"1190" 13,2005,9,1,12,15,3,982,2093.966,2099.176,2088.974,-0.001,-0.001,
  • -0.001,-0.000,0.001,-0.001,"11AC" 12,2005,9,1,12,20,4,82,2091.636,2099.117,2089.346,-0.001,-0.000,
  • -0.001,-0.001,-0
  • .001,-0.001,"115C" 11,2005,9,1,12,25,4,332,2092.435,2098.398,2088.487,-0.001,-0.001,

  • -0.001,-0.001,0.001,-0.001,"119C" 10,2005,9,1,12,30,4,36,2092.907,2098.208,2089.058,-0.001,-0.001,
  • -0.000,-0.001,-0
  • .001,-0.001,"115C" 9,2005,9,1,12,35,4,186,2093.153,2098.865,2089.091,-0.001,-0.000,

  • -0.001,-0.001,-0
  • .001,-0.001,"116F" 8,2005,9,1,12,40,3,978,2094.284,2098.926,2089.732,-0.001,-0.001,

  • -0.001,-0.001,-0
  • Figure 9 Excel Graph of Trend Data

    Page 6

    #### Transformer Thermal Monitoring

    Transformer thermal modeling per IEEE C57.91-1995 for mineral-oil immersed transformers is a standard feature in the SEL-2414. Specify the SEL-2414 to provide this capability for monitoring and protection of a single three-phase transformer, a three-phase transformer with tertiary windings (three-winding mode with separate CT ratios), or three independent single-phase units. Use the thermal element to activate a control action or issue a warning or alarm when your transformer overheats or is in danger of excessive insulation aging or loss-of-life.

    .001,-0.001,"1179"

    Figure 8 Comma-Separated File Format for Easy Display, Analysis, and Archiving

    Use the thermal event report to capture current hourly and daily data about your transformer. Operating temperature calculations are based on load currents, type of cooling system, and actual temperature inputs (ambient and top-oil). Use as many as four thermal sensor inputs: a single ambient temperature transducer and one transducer for top-oil temperature from each of three singlephase transformers. Temperature data are obtained via an internal RTD/thermocouple card or from an external SEL-2600A RTD Module. While the SEL-2414 can receive temperature data at any rate, the thermal element uses the temperature data once per minute.

    The thermal element operates in one of three modes, depending upon the presence or lack of measured temperature inputs: 1) measured ambient and top-oil temperature inputs, 2) measured ambient temperature only, and 3) no measured temperature inputs. If the device receives measured ambient and top-oil temperatures, the thermal element calculates hot-spot temperature. When the device receives a measurement of ambient temperature without top-oil temperature, the thermal element calculates the top-oil temperature and hot-spot temperature. In the absence of any measured ambient or top-oil temperatures, the thermal element uses a default ambient temperature setting that you select and calculates the top-oil and hot-spot temperatures. The device uses hot-spot temperature as a basis for calculating the insulation aging acceleration factor (FAA) and loss-of-life quantities. Use the thermal element to indicate alarm conditions and/or activate control actions when one or more of the following exceed settable limits:

    ➤ Top-oil temperature

    ➤ Winding hot-spot temperature

    ➤ Insulation aging acceleration factor (FAA)

    ➤ Daily loss-of-life ➤ Total loss-of-life

    Generate a thermal monitor report that indicates the present thermal status of the transformer. Historical thermal event reports and profile data are stored in the device in hourly format for the previous 24 hours and in daily format for the previous 31 days.

    The thermal model can be used even if a current card is not installed. Current magnitude data can be received by IEC 61850 or other communications protocols.

    #### Through-Fault Event Monitor

    A through fault is an overcurrent event external to the differential protection zone. Though a through fault is not an in-zone event, the currents required to feed this external fault can cause great stress on the apparatus inside the differential protection zone. Through-fault currents can cause transformer winding displacement leading to mechanical damage and increased transformer thermal wear because of mechanical stress of insulation components in the transformer. The SEL-2414 throughfault event monitor gathers current level, duration, and date/time for each through fault. The monitor also calculates a I2t and cumulatively stores these data per-phase. The SEL-2414 through-fault report also provides percent of total through-fault accumulated according to the IEEE Guide for Liquid-Immersed Transformer Through-FaultCurrent Duration, C57.109-1993. Use through-fault event data to schedule proactive transformer bank maintenance and help justify through-fault mitigation efforts. Apply the accumulated I2t alarm capability of the device to indicate excess through-fault current over time.

    #### Simplify Your Transformer Commissioning

    The SEL-2414 front panel simplifies commissioning and troubleshooting:

    ➤ View field data and calculated values

    ➤ Diagnose data flow problems in seconds instead of

    hours

    ➤ Dramatically reduce troubleshooting time ➤ Eliminate the need for out-of-service time

    Front-Panel Visualization and Control

    Ambient Temperature 24.0 deg C

    Top Oil Temperature 75.0 deg C

    Build your own custom displays. Rotating displays show device measurements and settings information based on userconfigured display points.

    Max Top Oil Temperature

    80.1 deg C

    LTC Oil Temperature 65.0 deg C

    Page 7

    ![image 11](2414_ds_20180321_images/imageFile11.png)

    Access device configuration, detailed I/O status, alarms, and measured values with easy-to-use controls for operator interface

    +85°C

    Large temperature range for installing in outdoor cabinets

    —40°C

    Powered properly and self-tests are okay

    Program LEDs to indicate control state

    Configure 7 programmable LEDs to indicate I/O activity and device status

    Program 4 pushbuttons to perform direct user controls

    EIA-232 Port

    Figure 10 Simplify Your Commissioning

    ![image 12](2414_ds_20180321_images/imageFile12.png)

    Make your own labels by hand or with included Microsoft® Word template

    Configuration and Commissioning Software

    The included ACSELERATOR QuickSet software program simplifies device configuration in addition to providing commissioning and analysis support for the SEL-2414.

    ➤ Access settings creation help online.

    ➤ Use the PC interface to remotely retrieve reports

    and other system data.

    ➤ Organize settings with the device database

    manager.

    ➤ Monitor analog data, device I/O, and logic point

    status during commissioning tests.

    ➤ Load and retrieve settings using a simple PC com-

    munications link.

    ➤ Remotely operate and monitor using the device

    overview as a virtual front panel.

    ➤ Analyze event records with the integrated wave-

    form and harmonic analysis tool.

    Page 8

    Settings–Develop Settings Offline With an Intelligent Settings Editor That Only Allows Valid Settings.

    Settings–Create SELOGIC Control Equations With a Drag and Drop Editor and/or Text Editor.

    ![image 13](2414_ds_20180321_images/imageFile13.png)

    ![image 14](2414_ds_20180321_images/imageFile14.png)

    HMI–Device Overview.

    ![image 15](2414_ds_20180321_images/imageFile15.png)

    Metering

    The SEL-2414 provides extensive metering capabilities. See Specifications for metering and power measurement accuracies. As shown in Table 1, metering includes current and voltage based metering and analog input, math variable, and remote analog metering. Fundamental, maximum and minimum, and demand metering typically includes phase voltages and currents; sequence voltages and currents; and power, frequency, and energy.

    Table 1 Metering Types Standard Fundamental IA, IB, IC, VA, VB, VC Energy Real, Reactive, Apparent (In and Out) Maximum and Minimum Frequency, Voltages (VA, VB, VC), Currents (IA, IB, IC, 3I2), Apparent, Reactive, and Real Power Demand and Peak Demand IA, IB, IC, IG, 3I2 Analog Input AIx01–AIx08 Math Variable MV01–MV32 Remote Analog RA001–RA128 Analog Signal Profiling Optional

    ➤ Temperature and thermal (with the external SEL-2600 RTD Module, internal RTD option, or internal RTD/TC option)

    ➤ Maximum and Minimum Temperatures

    Additional Ordering Options

    The following options can be ordered for any SEL-2414 model (see the SEL-2414 Model Option Table for details):

    Digital I/Oa 8 DI (PN 9760), 8 DO (PN9761), 4 DI/4 DO (PN 9764), 4 DI/3 DO with 2 Form C and 1 Form B (PN 9773) Analog I/O 8 AI (PN9762), 4 AI/4 AO (PN 9763) Temperatures 10 RTDs (PN 9772) CTs and PTs 3 ACI/3 AVI (PN 9771), 4CT (PN 9770), 3 AVI (PN 9769)

  • Port 1 Single/Dual 10/100BASE-T copper (RJ45 connector) Single/Dual 100BASE FX (LC connector)
  • Port 2 Fiber-Optic Port (62.5 m core fiber, ST connectors, SEL-2812 compatible) Port 4 EIA-232 or EIA-485 (PN 9751) Protocols Serial: DNP3; Ethernet: Modbus TCP, DNP3 LAN/WAN, FTP, Telnet, IEC 61850 Mounting Surface Mounting kit for in-cabinet installation (PN 915900204) Environment Conformal coating for chemically harsh and high-moisture environments a Unless otherwise specified, all digital outputs are Form A.
  • Automation

    #### Flexible Control Logic and Integration Features

    Replaces Traditional Temperature Gauges

    The SEL-2414 is equipped with as many as four independently operated serial ports: one EIA-232 port on the front, one EIA-232 or EIA-485 port on the rear, one fiber-optic port, and one EIA-232 or EIA-485 port option card. The device does not require special communications software. Use any system that emulates a standard terminal system for engineering access to the device. Establish communication by connecting computers, modems, protocol converters, printers, an SEL communications processor, SCADA serial port, and an RTU for local or remote communication. Apply an SEL communications processor as the hub of a star network, with point-to-point fiber or copper connection between the hub and the SEL-2414. Included communications protocols are listed below.

    Replace traditional temperature gauges that show the temperature, and the maximum and minimum temperature since last reset. The SEL-2414 Max/Min metering records and time stamps the maximum and minimum temperatures and transformer thermal model quantities.

    Replaces Traditional Latching Relays

    Replace as many as 32 traditional latching relays for such functions as “remote control enable” with latch bits. Program latch set and latch reset conditions with SELOGIC control equations. Set or reset the nonvolatile latch bits using optoisolated inputs, remote bits, local bits, or any programmable logic condition. The latch bits retain their state when the device loses power.

    Standard Protocols

    Eliminates External Timers

    ➤ Modbus RTU

    Eliminate external timers for custom protection or control schemes with 32 general purpose SELOGIC control equation timers. Each timer has independent time-delay pickup and dropout settings. Program each timer input with any desired element (e.g., time qualify a current element). Assign the timer output to control scheme logic.

    Page 9

    ➤ SEL ASCII

    ➤ SEL Compressed ASCII

    ➤ SEL Fast Meter

    ➤ SEL Fast Operate

    ➤ SEL Fast SER

    ➤ SEL Fast Message

    Eliminates RTU-to-Device Wiring

    ➤ SEL MIRRORED BITS

    Eliminate RTU-to-Device wiring with 32 remote bits. Set, clear, or pulse remote bits using serial port commands. Program the remote bits into your control scheme with SELOGIC control equations. Use remote bits for SCADA-type control operations such as trip and close.

    SEL-2414 logic improves integration in the following ways.

    Replaces Traditional Panel Control Switches

    Eliminate traditional panel control switches with operator control pushbuttons or the 32 local bits, available through the menu system. Program the four conveniently sized operator pushbuttons to control fan banks and fan lockout. Set, clear, or pulse local bits with the front-panel pushbuttons and display. Program the local bits into your control scheme with SELOGIC control equations. Use the local bits to perform functions such as breaker trip/close.

    Define custom messages to report station or device conditions with user-configured display points.

    FAN RUNNING

    SWITCH OPEN

    Replaces Traditional Indicating Panel Lights

    CONTROL ENABLE

    Replace traditional indicating panel lights with 32 programmable displays. Define custom messages (e.g., Fan On, Fan Off) to report transformer or device conditions on the front-panel display. Use advanced SELOGIC control equations to control which messages the device displays. Figure 11 shows an example.

    XFMR OVERLOAD

    Figure 11 Define Custom Messages to Report Station or Device Conditions

    #### Communications Architectures

    10/100BASE-T Ethernet Port

  • - Modbus TCP
  • - DNP3 LAN/WAN
  • - Telnet
  • - FTP
  • - IEC 61850
  • DCS or SCADA Master

    | | | |---|---|

    Page 10

    | | |

    Ethernet Switch

    ![image 16](2414_ds_20180321_images/imageFile16.png)

    ![image 17](2414_ds_20180321_images/imageFile17.png)

    ![image 18](2414_ds_20180321_images/imageFile18.png)

    ![image 19](2414_ds_20180321_images/imageFile19.png)

    EIA-485 DCS or SCADA Master

  • - Modbus RTU
  • - DNP3 Level 2 Slave
  • | | | | |---|---|---| | | | |

    ![image 20](2414_ds_20180321_images/imageFile20.png)

    ![image 21](2414_ds_20180321_images/imageFile21.png)

    ![image 22](2414_ds_20180321_images/imageFile22.png)

    ![image 23](2414_ds_20180321_images/imageFile23.png)

    (A) Ethernet Communications Architecture (B) EIA-485 Communications Architecture

  • Figure 12 Typical Ethernet and EIA-485 Communications Architectures
  • Figure 13 Typical EIA-232 and Fiber-Optic Communications Architecture
  • DCS or SCADA Master

    Local HMI

    EIA-232 or Fiber Optic

    ![image 24](2414_ds_20180321_images/imageFile24.png)

  • - Modbus RTU
  • - DNP3 Level 2 Slave
  • - SEL ASCII
  • - SEL Fast Message, Fast SER
  • - SEL Fast Meter, Fast Operate
  • Metallic or Fiber-Optic Serial Cable

    Page 11

    ![image 25](2414_ds_20180321_images/imageFile25.png)

    ![image 26](2414_ds_20180321_images/imageFile26.png)

    ![image 27](2414_ds_20180321_images/imageFile27.png)

    ![image 28](2414_ds_20180321_images/imageFile28.png)

    SEL RelaySEL Relay

    Front- and Rear-Panel Diagrams

  • Figure 14 Front Panel With Default Configurable Labels
  • Figure 15 Rear-Panel Connections and Labels
  • | | | | | | | | | | | |---|---|---|---|---|---|---|---|---|---| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |

    | | | | |---|---|---| | | | |

    Power Supply

  • 2 DI, 3 DO
  • Ethernet Fiber-Optic IRIG-B, EIA-232

    8 DI

    10 RTD

  • 3 CT/3 PT 8 DO
  • Slot C

    Expansion Slots

    Slot D

    | | | | | | | | | | |---|---|---|---|---|---|---|---|---|

    Page 12

    Slot E

    | | | | | |---|---|---|---| | | | | |

    Slot Z

    (A) Rear-Panel Layout (B) Side-Panel Input and Output Designations

    Dimensions

  • Figure 16 SEL-2414 Panel-Mount
  • Figure 17 SEL-2414 Surface-Mount Dimensions
  • | | | | |---|---|---| | | | |

    Specifications

    Compliance

    Designed and manufactured under an ISO 9001 certified quality

    management system UL, cUL: UL 508, CSA C22.2 No. 142 CSA: CSA C22.2 No. 61010-1 CE Mark: EMC Directive

    Low-Voltage Directive Hazardous Locations

    Complies with UL 1604, CSA 22.2

    No. 213, and EN 60079-15. General

    Approvals:

    Operating Temperature Range

    –40° to +85°C (–40° to +185°F), per IEC 60068-2-1 and 60068-2-2. Note: LCD contrast impaired for temperatures below –20°C and above

    +70°C (–4°F and +158°F, respectively). UL/CSA Conformal

    Coated: –40° to +75°C (–40° to +167°F)

    Operating Environment Pollution Degree: 2 Overvoltage Category: II Relative Humidity: 5–95%, noncondensing Maximum Altitude: 2000 m

    Dimensions

    See Figure 16 and Figure 17. Weight

    2.0 kg (4.4 lb) Frequency

    System Frequency: 50, 60 Hz Inputs

    Page 13

    AC Current Input Phase

    INOM INOM = 5 A INOM = 1 A Rated Range: 0.1–96.0 A 0.02–19.20 A

    (according to IEC 60255-5, 60664-1)

    Note: This is a linearity specification and is not meant to imply

    continuous operation. Continuous Thermal

    Rating: 15 A 3 A

    (according to IEC 60255-6, IEEE C37.90-1989)

    1 Second Thermal: 500 A 100 A

    (according to IEC 60255-6) Rated Frequency: 50/60 ±5 Hz 50/60 ±5 Hz Burden (per phase): <0.050 VA <0.002 VA Measurement Category: II

    AC Current Input Neutral

    INOM INOM = 5 A INOM = 1 A Rated Range: 0.05–10.00 A 0.01–2.00 A

    (according to IEC 60255-5, 60664-1) Note: This is a linearity specification and is not meant to imply

    continuous operation. Continuous Thermal

    15 A 3 A (according to IEC 60255-6,

    Rating:

    IEEE C37.90-1989)

    1 Second Thermal: 500 A 100 A

    (according to IEC 60255-6) Rated Frequency: 50/60 ±5 Hz 50/60 ±5 Hz Burden (per phase): <0.1 VA <0.01 VA Measurement Category: II

    AC Voltage Input (300 V)

    Rated Operating

    Voltage (Ue): 100–250 Vac Rated Insulation Voltage: 300 Vac 10-Second Thermal: 600 Vac Rated Frequency: 50/60 ±5 Hz Burden: <0.1 W

    DC Transducer (Analog) Inputs

    Input Impedance: Current Mode: 200  Voltage Mode: >10 k

    Input Range (Maximum): Current Mode: ±20 mA Voltage Mode: ±10 V

    Sampling Rate: At least 5 ms Step Response: 1 s Accuracy at 25°C:

    ADC: 16 bit With user calibration: 0.05% of full scale (current mode)

    0.025% of full scale (voltage mode)

    Page 14

    Without calibration: Better than 0.5% of full scale at 25°C Accuracy Variation With Temperature:

    ±0.015% per °C of full scale (±20 mA or ±10 V) DC Transducer (Analog) Inputs Extended Range Option

    Input Impedance:

    Voltage Mode: >10 k Input Range (Maximum):

    Voltage Mode: ±300 V Sampling Rate: At least 5 ms Step Response: 1 s Accuracy at 25°C:

    ADC: 16 bit With user calibration: 0.025% of full scale (voltage mode) Without calibration: Better than 0.5% of full scale at 25°C

    Accuracy Variation With Temperature: ±0.015% per °C of full scale (±10 V)

    CMRR Typical: 65 db at 60 Hz Optoisolated Control Inputs

    When Used With DC Control Signals:

    250 V ON for 200–275 Vdc OFF below 150 Vdc 220 V ON for 176–242 Vdc OFF below 132 Vdc 125 V ON for 100–135.5 Vdc OFF below 75 Vdc 110 V ON for 88–121 Vdc OFF below 66 Vdc 48 V ON for 38.4–52.8 Vdc OFF below 28.8 Vdc 24 V ON for 15–30 Vdc OFF for < 5 Vdc

    When Used With AC Control Signals:

    250 V ON for 170.6–275 Vac OFF below 106 Vac 220 V ON for 150.3–264 Vac OFF below 93.2 Vac 125 V ON for 85–150 Vac OFF below 53 Vac 110 V ON for 75.1–132 Vac OFF below 46.6 Vac 48 V ON for 32.8–60 Vac OFF below 20.3 Vac 24 V ON for 14–27 Vac OFF below 5 Vac

    Current Draw at Nominal

    DC Voltage: 2–4 mA (Except for 240 V, 8 mA) Rated Insulation Voltage: 300 Vac Rated Impulse

    Withstand Voltage (Uimp): 4000 V

    RTD Input Card Number of Channels: Ten 3-wire RTDs Input Type: Supports the following RTD types on each independent input.

    100  platinum (PT100) 100  nickel (NI100) 120  nickel (NI120) 10  copper (CU10)

    Measuring Range: –50°C to 250°C ADC Resolution: 24 bit Accuracy:

    CU10: ±1°C typical at 25°C PT100, NI100, NI120: ±1°C typical at 25°C CU10, PT100, NI100,

    NI120: ±2°C worst case Resolution: ±1°C Update Rate: <3 s

    CMRR (typical): 100 dBv Noise Rejection: Up to 1 Vrms 50/60 Hz

    Universal Temperature Input Card Number of Channels: Ten (thermocouples or 3-wire RTDs) Input Type: Supports the following RTD or TC types on each independent input.

    100  platinum (PT100) 100  nickel (NI100) 120  nickel (NI120) 10  copper (CU10) J, K, T, E

    Measuring Range RTDs: –50° to 250°C Thermocouples (TCs)

  • J: –200° to 1200°C
  • K: –200° to 1370°C T: –200° to 400°C E: –200° to 950°C
  • ADC Resolution: 24 bit Accuracy RTDs CU10: ±1°C typical at 25°C PT100, NI100, NI120,

    CU10: ±0.1°C typical at 25°C CU10, PT100, NI100,

    Page 15

    NI120: ±2°C worst case

    TCs J, K, T, E: ±1°C with field calibration

    ±3°C without field calibration Resolution: ±0.1°C Update Rate: <3 s

    CMRR (typical): 100 dBv Noise Rejection: Up to 1 Vrms 50/60 Hz Isolation

    Number of Banks: Two Banks (5 channels each) Max. Working

    Common Mode: 250 Vdc Cold Junction

    Compensation: Automatic

    Time-Code Input Format: Demodulated IRIG-B On (1) State: Vih 2.2 V Off (0) State: Vil  0.8 V Input Impedance: 2 k Accuracy: ±3 milliseconds

    Time-Code Input (SNTP)

    High-Priority Server Accuracy: ±5 ms

    Accuracy: ±25 ms Outputs

    General OUT103 is Form C Trip Output, all other outputs are Form A. Dielectric Test Voltage: 2000 Vac Impulse Withstand

    Voltage (Uimp): 4000 V

    Mechanical Durability: 10M no load operations DC Output Ratings

    Electromechanical Rated Operational

    Voltage: 250 Vdc Rated Voltage Range: 19.2–275 Vdc Rated Insulation Voltage: 300 Vdc Make: 30 A @ 250 Vdc per IEEE C37.90 Continuous Carry: 6 A @ 70°C; 4 A @ 85°C Continuous Carry

    (UL/CSA Derating with All Outputs Asserted): 5 A @ <60°C; 2.5 A 60 to 70°C

    Thermal: 50 A for 1 s Contact Protection: 360 Vdc, 40 J MOV protection across

    open contacts

    Operating Time (coil energization to contact closure, resistive load): Pickup or Dropout time  8 ms typical

    Breaking Capacity (10,000 operations) per IEC 60255-0-20:1974:

    24 Vdc 0.75 A L/R = 40 ms 48 Vdc 0.50 A L/R = 40 ms 125 Vdc 0.30 A L/R = 40 ms 250 Vdc 0.20 A L/R = 40 ms

    Cyclic Capacity

    24 Vdc 0.75 A L/R = 40 ms 48 Vdc 0.50 A L/R = 40 ms 125 Vdc 0.30 A L/R = 40 ms 250 Vdc 0.20 A L/R = 40 ms

    (2.5 cycles/second) per IEC 60255-0-20:1974:

    Fast Hybrid (high-speed high current interrupting) Make: 30 A Carry: 6 A continuous carry at 70°C

    4 A continuous carry at 85°C 1 s Rating: 50 A MOV Protection

    Page 16

    (maximum voltage): 250 Vac/330 Vdc

    Pickup Time: <50 s, resistive load Dropout Time: 8 ms, resistive load Update Rate: 1/8 cycle Breaking Capacity (10000 operations):

    48 Vdc 10.0 A L/R = 40 ms 125 Vdc 10.0 A L/R = 40 ms 250 Vdc 10.0 A L/R = 20 ms

    Cyclic Capacity (4 cycles in 1 second, followed by 2 minutes idle for thermal dissipation):

    48 Vdc 10.0 A L/R = 40 ms 125 Vdc 10.0 A L/R = 40 ms 250 Vdc 10.0 A L/R = 20 ms

    Note: Per IEC 60255-23:1994, using the simplified method of

    assessment.

    Note: Make rating per IEEE C37.90-1989. AC Output Ratings

    Electromechanical Maximum Operational Voltage (Ue) Rating: 240 Vac

    Insulation Voltage (Ui) Rating (excluding EN 61010-1): 300 Vac

    Utilization Category: AC-15 (control of electromagnetic loads >

    72 VA) Contact Rating Designation:

    B300 (B = 5 A, 300 = rated insulation

    voltage) Voltage Protection Across

    Open Contacts: 270 Vac, 40 J Rated Operational Current

    3A @ 120Vac 1.5 A @ 240 Vac

    (Ie):

    Conventional Enclosed

    Thermal Current (Ithe) Rating: 5 A

    Rated Frequency: 50/60 ±5 Hz Pickup/Dropout Time:  8 ms (coil energization to contact

    closure) Electrical Durability Make

    VA Rating: 3600 VA, cos = 0.3 Electrical Durability

    Break VA Rating: 360 VA, cos = 0.3

    Fast Hybrid (high-speed high current interrupting) Make: 30 A Carry: 6 A continuous carry at 70°C

    4 A continuous carry at 85°C 1 s Rating: 50 A MOV Protection

    (maximum voltage): 250 Vac/330 Vdc Pickup Time: <50 s, resistive load Dropout Time: 8 ms, resistive load Update Rate: 1/8 cycle Breaking Capacity (10000 operations):

    48 Vac 10.0 A L/R = 40 ms 125 Vac 10.0 A L/R = 40 ms 250 Vac 10.0 A L/R = 20 ms

    Cyclic Capacity (4 cycles in 1 second, followed by 2 minutes idle for thermal dissipation):

    Page 17

    48 Vac 10.0 A L/R = 40 ms 125 Vac 10.0 A L/R = 40 ms 250 Vac 10.0 A L/R = 20 ms

    Note: Per IEC 60255-23:1994, using the simplified method of

    assessment.

    Note: Make rating per IEEE C37.90-1989.

    Analog Outputs Current Ranges (Max): ±20 mA Voltage Ranges (Max): ±10 V Output Impedance For

    Current Outputs: 100 k Output Impedance For

    Voltage Outputs:  20  Maximum Load: 0–750  current mode

    >2k voltage mode Accuracy: ±0.55% of full scale at 25°C Step Response: 100 ms

    Communications

    Communications Ports

    Standard EIA-232 (2 ports) Location (fixed): Front Panel Rear Panel Data Speed: 300–38400 bps

    Optional Ethernet port: Single/Dual 10/100BASE-T copper (RJ45 connector) Single/Dual 100BASE FX Multimode (LC connector)

    Optional multimode fiber-optic serial port: Class 1 LED product Complies with IEC 60825-1:1993 + A1:1997 + A2:2001

    Fiber-Optic Ports Characteristics

  • Port 1 (or 1A, 1B) Ethernet Wavelength: 1300 nm Optical Connector Type: LC Fiber Type: Multimode Link Budget: 16.1 dB Typical TX Power: –15.7 dBm RX Min. Sensitivity: –31.8 dBm Fiber Size: 50–200 m Approximate Range: ~6.4 Km Data Rate: 100 Mb Typical Fiber Attenuation: –2 dB/Km
  • Port 2 Serial Wavelength: 850 nm Optical Connector Type: ST Fiber Type: Multimode Link Budget: 8 dB Typical TX Power: –16 dBm RX Min. Sensitivity: –24 dBm Fiber Size: 50–200 µm
  • Approximate Range: ~4 Km with 62.5 m,

    ~1 Km with 200 m Data Rate: 5 Mb Typical Fiber Attenuation: –4 dB/Km

    Optional Communications Card

    Standard EIA-232 or EIA-485 (ordering option)

    Data Speed: 300–38400 bps

    Communications Protocols

    Modbus® RTU slave or Modbus TCP DNP3 Level 2 Outstation (LAN/WAN and Serial) IEC 61850 Communications Ethernet FTP Telnet SEL MIRRORED BITS (MBA, MBB, MB8A, MB8B, MBTB) Ymodem file transfer on the front and rear port Xmodem file transfer on the front port SEL ASCII and Compressed ASCII SEL Fast Meter SEL Fast Operate SEL Fast SER SEL Fast Message unsolicited write SEL Fast Message read request SEL Event Messenger Points

    Maximum Concurrent Connections Modbus Slave: 1 DNP3 Level 2 Outstation: 3a Ethernet FTP: 2 Telnet: 2 a Maximum in any combination of serial and/or LAN/WAN links.

    Power Supply

    Rated Supply Voltage Low-Voltage Model: 24/48 Vdc High-Voltage Model: 110/250 Vdc

    110/230 Vac, 50/60 Hz

    Page 18

    Input Voltage Range Low-Voltage Model: 18–60 Vdc High-Voltage Model: 85–275 Vdc

    85–264 Vac

    Power Consumption AC: < 40 VA DC: <15 W

    Interruptions

    Low-Voltage Model: 10 ms @ 24 Vdc 50 ms @ 48 Vdc

    High-Voltage Model: 50 ms @ 125 Vac/Vdc

    100 ms @ 250 Vac/Vdc AC Metering Accuracies

    Current

    Phase Current: ±0.5% typical, 25°C, 60 Hz, nominal current

    Neutral Current: ±0.5% typical, 25°C, 60 Hz, nominal current

    Negative Sequence (3I2): ±0.5% typical, 25°C, 60 Hz, nominal current (calculated)

    Residual Ground Current: ±0.5% typical, 25°C, 60 Hz, nominal

    current (calculated) Voltage

    Line-to-Neutral Voltage: ±0.08% typical, 25°C, 60 Hz, nominal voltage

    Line-to-Line Voltage: ±0.08% typical, 25°C, 60 Hz, nominal voltage Negative-Sequence (3V2):

    ±0.5% typical, 25°C, 60 Hz, nominal voltage (calculated)

    Power

    Three-Phase Real Power

    (kW): ±1% typical, 25°C, 60 Hz, nominal voltage and current with 0.10 to 1.00 power factor

    Three-Phase Reactive

    Power (kVAR): ±1% typical, 25°C, 60 Hz, nominal voltage and current with 0.00 to 0.90 power factor

    Three-Phase Apparent Power (kVA): ±1% typical, 25°C, 60 Hz, nominal

    voltage and current Power Factor

    Three-Phase (wye connected): ±1% typical, 25°C, 60 Hz, nominal

    voltage and current (between 0.97 and 1) Sampling and Processing Specifications

    Without Voltage Card or Current Card

    Analog Inputs

    Sampling Rate: Every 4 ms Digital Inputs

    Page 19

    Sampling Rate: 2 kHz

    Contact Outputs Refresh Rate: 2 kHz Logic Update: Every 4 ms

    Analog Outputs Refresh Rate: Every 4 ms New Value: Every 100 ms Timer Accuracy: ±0.5% of settings and ±4 ms

    With Either Voltage Card, Current Card, or Both Voltage and Current Cards

    Analog Inputs

    Sampling Rate: 4 times/cycle Digital Inputs

    Sampling Rate: 32 times/cycle

    Contact Outputs Refresh Rate: 32 times/cycle Logic Update: 4 times/cycle

    Analog Outputs Refresh Rate: 4 times/cycle New Value: Every 100 ms Timer Accuracy: ±0.5% of settings and ±1/4 cycle

    Processing Specifications

    AC Voltage and

    Current Inputs: 16 samples per power system cycle Frequency Tracking Range: 44–66 Hz Digital Filtering: Cycle cosine after low-pass analog

    filtering. Net filtering (analog plus digital) rejects dc and all harmonics greater than the fundamental.

    Control Processing: 4 times per power system cycle or 4 ms if no current or voltage card (except for math variables and analog signals used in logic, which are processed every 100 ms)

    Type Tests

    Environmental Tests

    IP Code: IEC 60529:2001 IP34

    Vibration: IEC 60255-21-1:1988, Class 1 IEC 60255-21-3:1993, Class 2 IEC 60255-21-2:1988, Class 1

    Cold: IEC 60068-2-1:2007

    –40°C, 16 hours

    Damp Heat, Cyclic: IEC 60068-2-30:2005 25–55°C, 6 cycles, 95% relative humidity

    Dry Heat: IEC 60068-2-2:2007

    85°C, 16 hours Dielectric Strength and Impulse Tests

    Dielectric Strength: IEC 60255-5:2000 IEEE C37.90-2005

  • 2.5 kVac on analog inputs, contact I/O
  • 3.1 kVdc on power supply and analog outputs
  • Impulse: IEC 60255-5:2000

    Page 20

    0.5 J, 5.0 kV RFI and Interference Tests

    EMC Immunity Electrostatic Discharge Immunity: IEC 60255-22-2:2008 IEC 61000-4-2:2008

    Severity Level 4 8 kV contact discharge 15 kV air discharge

    Radiated RF Immunity: IEC 60255-22-3: 2007 IEC 61000-4-3:2010 10 V/m

    IEEE C37.90.2-2004, 35 V/m Fast Transient, Burst

    Immunity: IEC 60255-22-4:2008

    IEC 61000-4-4:2011 4 kV @ 5 kHz 2 kV @ 5 kHz for comm. ports

    Surge Immunity: IEC 60255-22-5:2008

    IEC 61000-4-5:2005 2 kV line-to-line 4 kV line-to-earth

    Surge Withstand Capability Immunity: IEC 60255-22-1:2007 2.5 kV common-mode

  • 1.0 kV differential-mode
  • IEEE C37.90.1-2002,

  • 2.5 kV oscillatory, 4 kV fast transient
  • Conducted RF Immunity: IEC 60255-22-6:2001, 10 Vrms

    IEC 61000-4-6:2006, 10 Vrms Magnetic Field Immunity:

    IEC 61000-4-8:2009 1000 A/m for 3 seconds 100 A/m for 1 minute

    EMC Emissions

    Conducted Emissions: IEC 60255-25:2000, Class A Radiated Emissions: IEC 60255-25:2000, Class A

    © 2008–2018 by Schweitzer Engineering Laboratories, Inc. All rights reserved.

    All brand or product names appearing in this document are the trademark or registered trademark of their respective holders. No SEL trademarks may be used without written permission. SEL products appearing in this document may be covered by U.S. and Foreign patents.

    2350 NE Hopkins Court • Pullman, WA 99163-5603 U.S.A. Tel: +1.509.332.1890 • Fax: +1.509.332.7990 selinc.com • [email protected]

    Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits afforded under federal and international copyright and patent laws in its products, including without limitation software, firmware, and documentation.

    ![image 29](2414_ds_20180321_images/imageFile29.png)

    The information in this document is provided for informational use only and is subject to change without notice. Schweitzer Engineering Laboratories, Inc. has approved only the English language document.

    This product is covered by the standard SEL 10-year warranty. For warranty details, visit selinc.com or contact your customer service representative.