Error Code CPF04

DC/DC Low Voltage alarm — the battery voltage has fallen below the minimum operating threshold.

? What Causes This

Battery voltage too low: less than 9V for 12V systems or less than 18V for 24V systems. May also indicate incorrect DIP switch setting for battery voltage selection.

How to Fix It

  1. For 12V systems: verify battery voltage is above 9V; for 24V systems verify voltage is above 18V.
  2. Check battery connections are secure and have no corrosion.
  3. Charge the battery using an external charger if voltage is too low.
  4. Verify DIP Switch 1 is correctly set for your system voltage (12V or 24V).
  5. If voltage remains low, the battery may be defective.

Source: page 45 of the official manual

From the manual

Manual page 45 — Upgraded error CPF04