How do I configure BACnet MS/TP or Modbus communication on the TC300?

To configure communication, navigate to Configuration > Connection. For BACnet MS/TP: tap BACnet MS/TP to enable it, then set a unique Device ID (different from other TC300 units). Auto-MAC addressing is enabled by default, or you can manually set a MAC address. You can manually configure the baud rate after an initial 5-minute delay; options include 9.6, 19.2, 38.4, 76.8, and 115.2 Kbps. For Modbus: tap Modbus to enable it and enter a unique address. Only one communication protocol (BACnet MS/TP or Modbus) can be enabled at a time. (Pages 81-84)