What operating temperature range is allowed for the SMVector drive?

The SMVector drive can operate in temperatures from -10°C to +55°C. Above +40°C, the output current must be derated by 2.5% for each degree Celsius increase, and the drive cannot exceed 55°C maximum.

From the official Lenze SMVector Variable Frequency Drive manual, page 6