error Honeywell
Error Code △!
Triangle symbol with exclamation mark indicating no HVAC partner found.
? What Causes This
HVAC partner has different address than default (14), or RF gateway device not configured with same Room ID, RF Channel, and PAN ID as e7w.
✓ How to Fix It
Verify HVAC partner address matches e7w settings or configure the RF Gateway device (PC502.4G) to use the same Room ID, RF Channel, and PAN ID. Refer to applicable commissioning documents.
Source: page 34 of the official manual