Honeywell Home Thermostat manual
Thermostats · 10 Q&As

Honeywell Home Thermostat

Ask AI

— answers from the official manual

AI-powered answers from the official manual. Verify critical info.

Common questions

Common Questions

10 total
1

Where can I find the Honeywell Home Thermostat Pro Series manual or PDF?

The TC300B Commercial Thermostat Configuration and User Guide (document 31-00644-02, Rev 05-24) is the primary manual for this thermostat. Additional reference documents include the TC300B Datasheet (31-00645), Mounting & Installation instructions (31-00642), Pocket guide (31-00648), BACnet Integration guide (31-00646), and Modbus Integration guide (31-00670). These documents provide comprehensive information for setup, configuration, and operation.

2

What are the safety precautions I should follow before installing the thermostat?

Before installation, keep the thermostat at room temperature for at least 24 hours to allow condensation from shipping to evaporate. Do not open the thermostat as it contains no user-serviceable parts. The device must be installed by authorized and trained personnel in accordance with the National Electric Code. Always assume hazardous voltages may exist in wiring systems and make a safety check with a voltage detection device before starting work.

3

How do I perform the initial setup of the TC300B thermostat?

The thermostat will power up automatically after mounting. You will navigate through guided setup screens including: Device Name, Network Connection, Temperature Units, Date & Time, Equipment Type, System Switch, Setpoints, and Installer Passcode. Follow the on-screen prompts and tap the arrows to proceed through each step. The setup process takes approximately 35 seconds to return to home screen if no interaction occurs.

4

What equipment types does the TC300B thermostat support?

The TC300B supports three main equipment types: Conventional (1H/1C), Heat Pump (2H/1C with air or water source), and Fan Coil (2-pipe or 4-pipe configurations). It also supports flexible I/O options for on/off valves, floating valves, modulating valves, 6-way modulating valves, and variable speed fans. The thermostat can be configured for dehumidification with reheat and auxiliary heating functions.

5

How do I change the temperature setpoint on the home screen?

On the home screen, you can adjust the temperature by touching the up arrow to increase the desired temperature or the down arrow to decrease it. The current desired temperature is displayed in the center of the screen. The actual indoor temperature is shown separately, along with the current system mode (heating or cooling).

6

What should I do if the display screen times out?

The display has automatic timeout properties: after 10 seconds of no activity, the backlight dims to 10% brightness. After 30 seconds, the display turns completely off (0% brightness) while the LED ring remains at 80% brightness to show operational status. The display will wake up instantly when you touch the screen. During initial setup, the system returns to the home screen after 35 seconds of inactivity.

Show 4 more questions

Full Manual

138 pages
Page 1

Configuration And User Guide

® U.S. Registered Trademark Copyright © 2024 Honeywell Inc. • All Rights Reserved 31-00644-02 | Rev 05-24 TC300B Commercial Thermostat

Connected Device For Commercial Buildings

Page 3

3 Table of contents Important Safety Information and Installation Precautions..................................8 Introduction................................................................................................................................... 11 About TC300B Thermostat............................................................................................... 12 Features.................................................................................................................................... 12 Intended audience and assumed knowledge............................................................ 13 Reference documents......................................................................................................... 13 Abbreviation and nomenclature..................................................................................... 14 Dimensions ............................................................................................................................. 14 Technical specifications..................................................................................................... 15 Terminal Identification ....................................................................................................... 20 Terminal assignment........................................................................................................... 22 Security requirement........................................................................................................... 23 Overview.......................................................................................................................................... 25 Home screen: Temperature reading and adjustment............................................ 26 Quick access screen (right side screen): Device configuration.......................... 27 Ambiance screen (left side screen): Sensor reading .............................................. 28 Home screen icon overview.............................................................................................. 28 Inactive display modes....................................................................................................... 30 Display timeout properties ............................................................................................... 30 Getting Started............................................................................................................................. 33 Prerequisites........................................................................................................................... 34 Guided set-up ........................................................................................................................ 35 Configuration................................................................................................................................ 43 Configuration screen .......................................................................................................... 44 Basic configuration.............................................................................................................. 45

Page 4

4

Tc300B Thermostat User Guide

Equipment configuration ..................................................................................................52 I/O terminal assignment....................................................................................................65 Sensors......................................................................................................................................68 System switch.........................................................................................................................73 Discharge air control ...........................................................................................................74 Dehumidification ..................................................................................................................77 Valve cycle................................................................................................................................77 Advanced configuration .....................................................................................................78 Setpoint options - All equipment types........................................................................79 Heat pump ...............................................................................................................................81 Cooling options - For Heat pump & Conventional equipment ...........................82 Cooling options - For Fan coil equipment...................................................................84 Heating options - For Heat and Conventional equipment...................................85 Heating options - For Fan coil equipment..................................................................86 Pipe sensor thresholds .......................................................................................................88 Valve purge ..............................................................................................................................89 Compressor delay time .......................................................................................................90 Miscellaneous ........................................................................................................................90 Service mode...........................................................................................................................91 Standby action .......................................................................................................................93 Security log..............................................................................................................................93 Diagnostics..............................................................................................................................94 Connection ..............................................................................................................................95 User management ................................................................................................................99 User roles..................................................................................................................................99 Home screen (Display management)........................................................................ 102 Display settings ..................................................................................................................103 Reset to default................................................................................................................... 105 System status ......................................................................................................................106 Setpoints................................................................................................................................107 System mode........................................................................................................................109 Fan speed ..............................................................................................................................110 Alarms ........................................................................................................................................... 111 Alarms..................................................................................................................................... 111

Page 5

5

Tc300B Thermostat User Guide

Alarm notification signs...................................................................................................111 Alarm notification...............................................................................................................112 Alarm preference ................................................................................................................112 Unacknowledged alarms.................................................................................................116 List of alarms and their severity ...................................................................................118 Managing the alarms........................................................................................................119 Scheduling...................................................................................................................................123 About schedule....................................................................................................................123 Weekly schedule..................................................................................................................124 Holiday schedule ................................................................................................................129 Special event ........................................................................................................................135

Page 6

6

Tc300B Thermostat User Guide

Page 7

7

Tc300B Thermostat User Guide

Declaration This document contains Honeywell proprietary information. Information contained herein is to be used solely for the purpose submitted, and no part of this document or its contents shall be reproduced, published, or disclosed to a third party without the express permission of Honeywell International Inc. While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a purpose and makes no express warranties except as may be stated in its written agreement with and for its customer. In no event is Honeywell liable to anyone for any direct, special, or consequential damages. The information and specifications in this document are subject to change without notice. Copyright 2024 – Honeywell International Inc. Waste Electrical and Electronic Equipment (WEEE) FCC Part 15 compliant This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. WEEE: Waste Electrical and Electronic Equipment Directive • At the end of the product life, dispose of the packaging and product in an appropriate recycling center. • Do not dispose of the device with the usual domestic refuse. • Do not burn the device.

Page 8

8 Important Safety Information and Installation Precautions

Tc300B Thermostat User Guide

Regulation (EC) No 1907/2006 According to Article 33 of Reach Regulation, be informed that the substances listed below may be contained in these products above the threshold level of 0.1% by weight of the listed article. Important Safety Information and Installation Precautions Read all instructions Failure to follow all instructions may result in equipment damage or a hazardous condition. Read all instructions carefully before installing equipment. When performing any work (installation, mounting, start-up), all manufacturer instructions and in particular the Mounting Instructions (31-00642) are to be observed. • TC300B Thermostat may be installed and mounted only by authorized and trained personnel. • It is recommended that devices be kept at room temperature for at least 24 hours before applying power. This is to allow any condensation resulting from low shipping/storage temperatures to evaporate. • Do not open TC300B Thermostat, as it contains no user-serviceable parts inside! • Investigated according to United States Standard UL- 60730-1, and UL60730-2-
  • Investigated according to Canadian National Standard(s) C22.2, No. 205-M1983 (CNL-listed). • For TC300B-G, CE declarations according to EMC Directive 2014/30/EU. • Product standards are EN 60730-1 and EN 60730-2-9. • TC300B Thermostat is Class B digital apparatus and complies with Canadian

    Ices-003.

    Local codes and practices Always install equipment in accordance with the National Electric Code and in a manner acceptable to the local authority having jurisdiction. Electrostatic sensitivity This product and its components may be susceptible to electrostatic discharge (ESD). Use appropriate ESD grounding techniques while handling the product. When possible, always handle the product by its non-electrical components. High voltage safety test Experienced electricians, at first contact, always assume that hazardous voltages may exist in any wiring system. A safety check using a known, reliable voltage measurement or detection device should be made immediately before starting work and when work resumes. Product/Part Code Substance Name CAS Number Only TC300B thermostat main board PCBA Lead 7439-92-1 Lead oxide 1317-36-8

    Page 9

    Important Safety Information and Installation Precautions 9

    Tc300B Thermostat User Guide

    Lightning and high-voltage danger Most electrical injuries involving low-voltage wiring result from sudden, unexpected high voltages on normally low voltage wiring. Low-voltage wiring can carry hazardous high voltages under unsafe conditions. Never install or connect wiring or equipment during electrical storms. Improperly protected wiring can carry a fatal lightning surge for many miles. All outdoor wiring must be equipped with properly grounded and listed signal circuit protectors, which must be installed in compliance with local, applicable codes. Never install wiring or equipment while standing in water. Wiring and equipment separations All wiring and controllers must be installed to minimize the possibility of accidental contact with other potentially hazardous and disruptive power and lighting wiring. Never place 24VAC or communications wiring near other bare power wires, lightning rods, antennas, transformers, or steam or hot water pipes. Never place wire in any conduit, box, channel, duct or other enclosure containing power or lighting circuits of any type. Always provide adequate separation of communications wiring and other electrical wiring according to code. Keep wiring and controllers at least six feet from large inductive loads (power distribution panels, lighting ballasts, motors, etc.). Failure to follow these guidelines can introduce electrical interference and cause the system to operate erratically. Warning By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use, or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys' fees, arising out of, or resulting from, any modification to the literature by you. The material in this document is for information purposes only. The content and the product it describes are subject to change without notice. Honeywell makes no representations or warranties with respect to this document. In no event shall Honeywell be liable for technical or editorial omissions or mistakes in this document, nor shall it be liable for any damages, direct or incidental, arising out of or related to the use of this document. No part of this document may be reproduced in any form or by any means without prior written permission from Honeywell. Safety Information as per EN60730-1 TC300B Thermostat is intended for commercial and residential environments. TC300B Thermostat is an independently mounted electronic control system with fixed wiring. TC300B Thermostat is used for the purpose of building HVAC control and is suitable for use only in non-safety controls for installation on or in appliances.

    Page 10

    10 Important Safety Information and Installation Precautions

    Tc300B Thermostat User Guide

    Page 11

    Chapter

    1 11 Introduction This chapter contains brief description of the TC300B thermostat and its hardware specifications. Related topics About TC300B Thermostat Features Intended audience and assumed knowledge Reference documents Abbreviation and nomenclature Dimensions Technical specifications Terminal Identification Terminal assignment Security requirement

    Page 12

    12 About TC300B Thermostat

    1 - Introduction

    About TC300B Thermostat TC300B Thermostat is an advanced, highly configurable device providing building automation connectivity well-suited for indoor commercial building applications. It has flexible I/O options that will satisfy the needs of 1H/1C conventional, 2H/1C heat pump, and most 2-pipe or 4-pipe fan coil applications. Supported functions include dehumidification with reheat using an embedded humidity sensor, auxiliary heat functions, and more rapid transitional 2-pipe system seasonal changeover. TC300B supports BACnet MS/TP and Modbus communications via RS485 bus as is needed for typical HVAC building control systems. The same bus facilitates future firmware updates and enhanced functionality as they are released to the market. The integral intelligent control algorithms plus scheduling help to achieve the perfect balance between Energy Efficiency and Comfort. It utilizes an attractive, color, capacitive-touch screen interface providing an intuitive configuration process with minimal installer training. This functionality is enhanced through embedded help screens reducing reliance on technical manuals for complex installation. Features Convenient for users • Color, capacitive-touch screen display for intuitive, fast commissioning and exceptional user experience. • Embedded system monitoring screen for equipment and I/O status. • Customizable inactive display modes, Auto dim display, always on, or dark mode. • An LED ring indicator to show the operational status. • Real-Time Clock time-keeping accuracy with 72-hour retention during power loss. Easy for contractors • 2H/1C Heat pump, 1H/1C Conventional-Water Source Heat Pump with water valve enable/lock-out, Fan coil, On/Off Valve, Floating Valve, Modulating Valve, and 6-Way Modulating Valve. • 1-3 or variable speed fan • Dehumidification with and without reheat. • Enhanced 2-pipe fan coil functionality during seasonal or system changeover delivering improved occupant comfort. • Service mode for manually enabling outputs for quicker diagnostics and equipment testing. • Auxiliary heating options supporting peripheral or supplemental types • Auto mode to switch between heating and cooling according to the current space temperature • Staging control, PID Tuning, DAT Lockout, Modulating control, Compressor time delay • System Switch and Ventilation options. • Integration with various external wired sensor types including Discharge air temperature, Drain pan, Occupancy, Proof of airflow, Proof of water flow, Space temperature, Outdoor air temperature, CO2, and Humidity. • Complies with ASHRAE guideline 36-2021, Section 5.22 sequence of operations for high- performance operation when using floating/modulating valves and multi-speed/variable speed fan. • Advanced commercial control algorithms such as auto changeover.

    Page 13

    Intended audience and assumed knowledge 13

    Intended Audience And Assumed Knowledge

    Connected for facility managers • Thermostat can be configured via its own LCD human-machine interface (HMI) or a BACnet/Modbus client. • Multiple, configurable user types with customizable privileges to prevent unauthorized usage. • Customizable daily schedules include options for setting up to 10 recurring holidays (with support for floating holidays) and up to 10 specific special events. • Up to 4 schedule events per day. Intended audience and assumed knowledge This document provides information about installing and commissioning a TC300B/ Thermostat. It also shows how to operate the user interface. It is assumed that the user is trained and familiar with HVAC concepts. IMPORTANT: Always install equipment in accordance with the National Electric Code and in a manner acceptable to the local authority having jurisdiction (AHJ). No guidelines, instructions, installation practices, or other information presented in this guide may be interpreted to supersede or modify the local codes and practices of the

    Ahj.

    Reference documents • TC300B Commercial Thermostat Datasheet (31-00645) • TC300B Commercial Thermostat Mounting & Installation instructions (31-00642) • TC300B Commercial Thermostat Pocket guide (31-00648) • TC300B Deco Plate Pocket guide (31-00657) • TC300B BACnet Integration guide (31-00646) • TC300B Modbus Integration guide (31-00670)

    Page 14

    14 Abbreviation and nomenclature

    1 - Introduction

    Abbreviation and nomenclature Dimensions Thermostat Figure 1 Dimensions Abbreviation Definition

    Ahu

    Air Handling Unit

    Vac

    Volts AC (Alternating Current)

    Vdc/ Dc

    Volts DC (Direct Current)

    Bms

    Building Management System

    Hmi

    Human Machine Interface

    Dat

    Discharge Air Temperature

    Oat

    Outdoor Air Temperature 3.93” (100mm) 4.47” (113.6 mm) 1.02” (26mm) 0.76” (19.4mm)

    Page 15

    Technical specifications 15

    Technical Specifications

    Trtc-Decoplate-1

    Technical specifications Electrical Characteristics 5.51” (140 mm) 5.51” (140 mm) 0.27” (7 mm) Table 1: Power Characteristics Power Supply Rated voltage: 24VAC 50/60Hz, Working voltage range: 20-30VAC, UL listed class-2 transformer or IEC 61558 listed transformer. Power Consumption (Display ON) TC300B: Max. 8.5VA@24VAC (355mA@24VAC) Min. Load 4VA (all DOs OFF, No Sylk sensor) Max. Load 96VA (all DOs ON) Rated Impulse Voltage

    500 V

    Pollution Degree 2 Relay Type Type 1, Form B

    Page 16

    16 Technical specifications

    1 - Introduction

    Display Operating Environment Compliances Table 2: Display Display Type 16 BPP TFT display with CTP Resolutions 320*240 pixel Active Display Area 2.4” diagonally Backlight LCD (Dimmable) LED Color Ring Blue (cooling) Orange (heating) Table 3: Operating Environment Ambient Operating Temperature Range: 32 to 122 °F (0 to 50°C) Ambient Operating Humidity 10 to 90% relative humidity (non-condensing) Storage Temperature -40 to 150 °F(-40 to 65.5°C) Protection Class

    Ip20

    Table 4: Compliances Certificates •

    Ce

    Fcc

    Ices

    • UL/cUL • RoHs •

    Reach

    • Prop65 Standards •

    En 60730-1

    En 60730-2-9

    Ul60730-1

    Ul60730-2-9

    • Title 47 part 15 subpart B •

    Ices-003

    Page 17

    Technical specifications 17

    Technical Specifications

    IO Characteristics Onboard Sensors Table 5: IO Characteristics UIO x 3 • Resistive Temperature Sensor Input — NTC10K Type II, C7021 series — NTC10K Type III, C7023 series — NTC20K, TR21, and C7041 series • Digital Input — Dry contact closure — Open circuit (≥ 100Kohms) — Closed circuit (≤100ohms) • Voltage Output — 0-10V, ±3% of full scale @2K ohms DIO x 2 • Resistive Temperature Sensor Input — NTC10K Type II, C7021 series — NTC10K Type III, C7023 series — NTC20K, TR21, and C7041 series • Digital Input — Dry contact closure — Open circuit (≥ 100Kohms) — Closed circuit (≤100ohms) DO x 3 DIO x 2 • Relay Output • Rated Average Current — 1A Resistive at 24VAC • Rated Pulse Current — 3.5A Resistive at 24VAC Table 6: Onboard Sensors Temperature Range: 32 to 122 °F (0 to 50 °C) Resolution: 1 °F (0.5°C) Control Accuracy: ±1.5°F (0.8°C) at Room Temperature Humidity Range: 20~90% RH Resolution: 1%RH Accuracy: ±5%RH at Room Temperature

    Page 18

    18 Technical specifications

    1 - Introduction

    Communication Technologies Supported Sensors and Functions Table 7: Communication Technologies SylkTM Honeywell SylkTM BACnet MS/TP RS485 (9.6, 19.2, 38.4, 76.8, 115.2 Kbps) Modbus RTU RS485 (1.2 to 115.2 Kbps) Table 8: Supported Sensors Sensors Options Part Numbers Occupancy Sensor Direct (Normally Open) Reverse (Normally Closed) Dry contact occupancy sensor Proof Of Air Flow Sensor Direct (Normally Open) Reverse (Normally Closed)

    Dps200

    Dps400

    Dps1000

    MCS, CS, CSP current switches (Dry contact switches) Discharge Air Temperature Sensor

    Ntc 20K

    NTC 10K Type II NTC 10K Type III Sylk

    C7250A

    C7041

    C7021

    C7023

    C7400S

    Space Temperature Sensors

    Ntc 20K

    NTC 10K Type II NTC 10K Type III Sylk

    Tr21

    C7041, C7772A, C7021, C7772F,

    C7023, C7772G,

    Tr40,

    Tr40-H,

    Tr40-Co2,

    Tr40-H-Co2,

    Tr50-3N, Tr50-3D

    Changeover Pipe Sensor NTC 20K NTC 10K Type II NTC 10K Type III

    C7250A

    C7041

    C7021

    C7023

    Changeover Switch Closed with heat Closed with cool Digital input Drain Pan / Leak Detector Direct (Normally Open) Reverse (Normally Closed Dry contact float switch or water sensor Proof of Water Flow Sensor Direct (Normally Open) Reverse (Normally Closed) Dry contact pressure switch

    Page 19

    Technical specifications 19

    Technical Specifications

    Part Numbers Table 9: Part Numbers

    Tc300B-G

    RS485 BACnet MS/TP and Modbus

    Trtc-Decoplate-1

    Decorative wall plate, TR and TC Series

    Page 20

    20 Terminal Identification

    1 - Introduction

    Terminal Identification Table 10: Terminal Identification Terminal Name Terminal Label Description

    Uio1

    Uio1

    Universal input/output

    Com

    Com

    Common

    Uio2

    Uio2

    Universal input/output

    Com

    Com

    Common

    Uio3

    Uio3

    Universal input/output

    Rs485 Slave

  • BACnet/Modbus
  • Communications

    Rs485 Slave

    + BACnet/Modbus Communications

    Sylk Master

    Sylk bus

    Sylk Master

    Sylk bus

    Page 21

    Terminal Identification 21

    Terminal Identification

    Do1

    Do1

    Configurable relay output

    Do2

    Do2

    Configurable relay output

    Do3

    Do3

    Configurable relay output

    Dio1

    Dio1

    Configurable relay output, configurable analog/relay input

    Dio2

    Dio2

    Configurable relay output, configurable analog/relay input

    24Vac Power

    R

    24VAC power from Class2 transformer

    24Vac Power

    C

    24VAC common (Neutral) from Class2 transformer

    Com

    Com

    Common Table 10: Terminal Identification (Continued) Terminal Name Terminal Label Description

    Page 22

    22 Terminal assignment

    1 - Introduction

    Terminal assignment Table 11: Terminal assignment Type Terminal Label Terminal Assignments Default Inputs Outputs Digital Output

    Do1

    Do1

    On/Off Heat

    Na

    Heating On/Off, Heating Floating Open, Cooling Floating Open, Valve On/Off, Valve Floating Open, FCU Changeover Valve, Fan Command, High Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat, Conventional Heat Stage 1, Valve Stage 1, Heat Pump. Heat/Cool Note: FCU Changeover valve used to switch between heating and cooling modes

    Do2

    Do2

    On/Off Cool

    Na

    Heating Floating Close, Cooling Floating Close, Cooling On/Off, Valve Floating Close, FCU Changeover Valve, Fan Command, High Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat, Conventional. Cool Stage 1, Reversing Valve

    D03

    Do3

    Na

    Na

    Cooling Floating Heat Pump. Reversing Valve, FCU Changeover Valve, Fan Command, High Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat, Heat Stage 1, Cool Stage 1, Water Source Heat Pump Water Valve

    Dio1

    Dio1

    Na

    Discharge Air Sensor, Drain Pan Sensor, Occupancy Sensor, Proof of Air/Water Flow, Pipe Sensor, Space Temp Sensor, Changeover Switch Cooling Floating Close, FCU Changeover Valve, Fan Command, High Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat

    Dio2

    Dio2

    Na

    Discharge Air Sensor, Drain Pan Sensor, Occupancy Sensor, Proof of Air/Water flow, Pipe Sensor, Space Temp Sensor, Changeover Switch FCU Changeover Valve, Fan Command, High Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat Universal Input/ Output

    Uio1

    Uio1

    Na

    Discharge Air Sensor, Drain Pan Sensor, Occupancy Sensor, Proof of Air/Water flow, Pipe Sensor, Space Temp Sensor, Changeover Switch 6-Way Valve, Modulating Cool, Modulating Heat, Modulating Valve, UIO2 UIO2 NA Variable Speed Fan

    Uio2

    Uio2

    Na

    Uio3

    Uio3

    Na

    Page 23

    Security requirement 23

    Security Requirement

    Security requirement System Environmental Considerations An Internet firewall is required to isolate the Thermostat. Unprotected Internet connections can expose and damage the thermostat system and facility components to cyber-attacks from third parties. This may cause the thermostat to malfunction and can also be misused for illegal purposes for which the operator may then be held liable. Deployments and Maintenance Considerations • Always keep the local server up to date on the latest security patches via a regular system update. This applies not only to workstations or servers running on Windows, Linux, Mac, or any devices that run as part of information infrastructure or operations workstation. • Always keep the thermostat firmware with the latest released firmware to have maximum protection by built-in security features. • Do not use default passwords for any devices (if exists). This includes, but not limited, to all server workstations, storage servers, firewall devices, routers, and mobile devices. • Do not use weak passwords for server administrators or operators. Different user roles (for example administrator, user, guest, etc.) shall have a different password, and the user should not share common passwords. • In case of wireless communication, malicious wireless devices can easily scan the wireless channel and inject malicious packets or mass data flow to perform Denial-of-Service attacks. Honeywell has taken steps to prevent the TC300B Commercial Thermostat device from being injected, but the mass data flow will result in the loss of wireless communication bandwidth within the whole system. A regular check of the communication failure rate or response rate of the thermostat is helpful to discover and isolate devices being attacked and stop the physical attacks in the daily operation Network Communication Notice • To keep maximum integration compatibility with third-party devices and Fast-pack communications are un-encrypted as open protocol. Improper security protection may lead to data leakage, spoofing, and/or tampered by malicious devices and denial-of- service attacks. • To keep maximum integration compatibility with legacy devices, in-room wired devices are less secure from data confidentiality and authentication thus not-recommended for a new design. It is always highly recommended to use deep mesh wireless network communication to gain maximum protection and the latest updates. • In case of Denial-of-Service attacks, all communication channels will inevitably have a loss of bandwidth due to malicious data flow. • Connected devices may contain legacy technology, which is less secure under modern cyber-security attacks. Honeywell strongly recommends using a secured deep mesh wireless network communication. In case of legacy technology, the user needs to be aware of the risk of being tampered with or attacked. To reduce the attack surface, the user is advised to physically secure the wired communication signals or provide necessary shield on wires, or place necessary access control on accessing such communication wires.

    Page 24

    24 Security requirement

    1 - Introduction

    Page 25

    Chapter

    2 25 Overview This chapter describes the TC300B Thermostat display, home screens, icons, and other user interfaces. For mounting the TC300B Thermostat, refer to TC300B Thermostat Mounting instructions (31-00642). Related topics Home screen: Temperature reading and adjustment Quick access screen (right side screen): Device configuration Ambiance screen (left side screen): Sensor reading Home screen icon overviewActive display modes Active display modes Display timeout properties

    Page 26

    26 Home screen: Temperature reading and adjustment

    2 - Overview

    Home screen: Temperature reading and adjustment Table 12: Home screen (main screen) Overview Item Description 1 Time 2 Alarm status 3 Adjust temperature: Touch the up arrow to increase the desired temperature. 4 Desired temperature: Displays the desired temperature. 5 Adjust temperature: Touch the down arrow to decrease the desired temperature. 6 Fan Speed: Indicates current Fan speed for Fan Coil unit. Tap to change the fan speed. 7 Home screen indicator: Use finger to swipe to left or right to display more options. 8 System Mode Display: Orange flame for heat mode, blue snowflake for cool mode. 9 Indoor Temperature: Displays the current indoor temperature. 10 Current Schedule: Indicates the current Occupant status (Occupied, Unoccupied, Standby, Temporary) 11 Humidity: Indicates the current humidification/dehumidification status. 10 9 8 1 3 4 5 7 6 2 11

    Page 27

    Quick access screen (right side screen): Device configuration 27

    Quick Access Screen (Right Side Screen): Device Configuration

    Quick access screen (right side screen): Device configuration Swipe left from the home screen to view the Quick access screen. Table 13: Quick access screen Item Description 1 The name assigned to the thermostat while performing initial setup. 2 Override: Override unoccupied or standby modes to allow setpoint adjustments. 3 Setpoint: Configure the set points of various parameters. 4 Config: Configure the thermostat. 5 System Status: See the system status of various equipment 6 Brightness: Adjust the display brightness. 7 Alarm: View active alarms. 8 Schedule: Set the schedules. 9 Temperature Units: Switch between Fahrenheit or Celsius. 10 Help icon: User help information for the options available on the screen. 6 7 4 3 9 1 2 5 8 10

    Page 28

    28 Ambiance screen (left side screen): Sensor reading

    2 - Overview

    Ambiance screen (left side screen): Sensor reading Swipe right from the home screen to view the Ambiance screen. Establish Internet connection with thermostat, setup the location or connect to indoor sensors to dis- play the humidity and outdoor temperature. Figure 2 Ambiance screen (left side screen) Note: The types of reading displayed varies according to the sensor connected to the thermostat. To configure the ambiance screen, see Home screen (Display management). Home screen icon overview Table 14: Typical ambiance screen Description Indoor CO2 level (ppm) (Future feature release) Indoor humidity% Table 15: Home Screen Icon Overview Icon Description High severity alarm Medium severity alarm Auto mode Heating mode

    Page 29

    Home screen icon overview 29

    Home Screen Icon Overview

    EMER heat mode Cooling mode Humidification Dehumidification Ventilation mode (Fan only) System off Fan auto Fan speed low Fan speed medium Fan speed high Fan circulate Occupied mode Standby mode Unoccupied mode Temporary mode Permanent mode Table 15: Home Screen Icon Overview Icon Description

    Page 30

    30 Inactive display modes

    2 - Overview

    Figure 3 Active display modes Inactive display modes Figure 4 Inactive display modes Note: To configure the ring LED and display, see Display settings. Display timeout properties Table 16: Display timeout properties LCD back light behavior Time Mode LCD back light brightness (0-100, pwm) LED back light brightness (0-100, pwm) Wakes up when user touch the screen Instant Normal/Disable LCD Off/Enable dark mode 80% 10% Dimmer when no user activity In 10 seconds Normal/Disable LCD Off/Enable dark mode 10% 10%

    Page 31

    Display timeout properties 31

    Display Timeout Properties

    Off/black when no user activity In 30 seconds Normal 0% 80% Disable LCD off 10% 80% Enable dark mode 0% 0% Return to home screen - During initial setup In 35 seconds
  • -
  • Table 16: Display timeout properties (Continued)
  • LCD back light behavior Time Mode LCD back light brightness (0-100, pwm) LED back light brightness (0-100, pwm)

    Page 32

    32 Display timeout properties

    2 - Overview

    Page 33

    Chapter

    3 33 Getting Started This chapter contains steps and descriptions to set up the initial configuration of the thermostat and other basic configurations. Related topics Prerequisites Guided set-up

    Page 34

    34 Prerequisites

    3 - Getting Started

    Prerequisites Before going through initial guided setup sequences, ensure the TC300B is installed and wired up according to the TC300B installation and mounting guide.

    Warnings

    • To reduce the risk of electrical shock do not open the thermostat. There are no user- serviceable parts inside. Refer servicing to qualified service personnel only. • Cleaning — Use a dry cloth to clean the product. Do not use liquid cleaners or aerosol cleaners • Water and moisture — Do not use the product near water. Do not install the product in a place where water may splash onto it. • Do not operate the thermostat with a hard, sharp, or pointed object such as a fingernail, pen. • The screen used for the thermostat is made of glass. Therefore, it can break when the product is dropped or heavy impact is applied. Do not handle broken glass without appropriate protection in event of damage.

    Page 35

    Guided set-up 35

    Guided Set-Up

    Guided set-up The thermostat will be powered up automatically after it mounted on the wallplate. You will navigate through the settings given below subsequently while setting up the thermostat. The Device Name appears.Naming thermostat Connecting to network Temperature units Date and Time Equipment type System switch Installer Passcode Service Info To set up the thermostat
  • Power-up the thermostat.
  • The Honeywell logo screen appears, followed by the “Welcome to TC300” screen. Figure 5 Welcome screens The Welcome screen followed by the LET’S BEGIN screen appears. Figure 6 Welcome screen

    Page 36

    36 Guided set-up

    3 - Getting Started

  • Tap LET’s BEGIN.
  • The Device Name appears.Naming thermostat Figure 7 Device Name
  • Tap on the text field
  • A keyboard will be displayed on the screen to enter the device name.
  • Enter the device name.
  • Assign a unique name to a thermostat specifying a name to the location where the thermostat is installed. It assists the user to easily identify the device during remote operation of the thermostat.
  • After entering a valid device name tap the right arrow button.
  • The device name is saved and the Connection screen appears. Connecting to network Figure 8 Connection
  • If no connection is required, tap SKIP or tap the right arrow button.
  • If connection is required, the connection screen appears.

    Page 37

    Guided set-up 37

    Guided Set-Up

    Figure 9 Connection
  • Tap BACnet MS/TP and enable the MSTP connection. See Connection.
  • Tap Modbus and enable the Modbus connection. See Connection.
  • The General screen appears. Temperature units Figure 10 Temperature unit
  • Select a preferred temperature unit.
  • Set the Date & Time. See Date and Time
  • Page 38

    38 Guided set-up

    3 - Getting Started

    Date and Time Figure 11 Date and Time Configuration screen
  • Tap the date to set the today’s date.
  • Slide the Display toggle button to the right to set the 24h time format if required.
  • Enable Daylight Savings if required.
  • If Daylight saving is enabled, set the start and end date schedules for daylight savings.
  • After setting date and time, navigate back to General screen and tap the right arrow
  • button. The Equipment and I/O screen appears. Equipment type The TC300B is designed to control Conventional, Heat pump, and Fan coil units (FCU) equipment. It can control 1H/1C conventional, 2H/1C heat pump, and most 2-pipe or 4-pipe fan coil applications. Figure 12 Equipment and I/O
  • Tap Equipment and set the equipment details. See Equipment configuration.
  • Tap I/O Assignment and assign the I/Os. See I/O terminal assignment.
  • Page 39

    Guided set-up 39

    Guided Set-Up

  • Tap the right arrow button.
  • The System Switch screen appears. System switch The operation mode of system switch depends on the equipment configuration. Figure 13 System Switch
  • Set the required parameters and tap the right arrow button.
  • The Setpoints screen appears. Figure 14 Setpoints

    Page 40

    40 Guided set-up

    3 - Getting Started

  • Configure the Occupied, Standby, and Unoccupied setpoints.
  • After configuring the setpoints, tap the right arrow button on the Setpoint screen to move
  • to next screen. The Passcode screen appears. Installer Passcode Figure 15 Passcode
  • Tap on the text field
  • A keyboard will popup.
  • Enter a passcode.
  • Note: The passcode must contains 4 to 12 characters including a Alpha/numeric/symbol character.
  • Tap the right arrow button.
  • The Service Info screen appears. Note: The Installer passcode is to prevent unauthorized changes to thermostat settings. This passcode will be needed to enter into locked menu's, such as Advanced Configuration. Service Info Figure 16 Service Info
  • Enter the service personnel information.
  • Page 41

    Guided set-up 41

    Guided Set-Up

  • Tap the right arrow button.
  • The Congratulations message appears. Figure 17 Successful connection
  • Tap DONE.
  • The User Management screen appears. Figure 18 User management
  • Tap YES to configure the user list. See User management.
  • Tap No to start using the thermostat.
  • Thermostat Home screen appears. Figure 19 Home screen

    Page 42

    42 Guided set-up

    3 - Getting Started

    After set up the thermostat device, you can re-configure the user management equipment, schedules, alarms, and terminal assignments.

    Page 43

    Chapter

    4 43 Configuration This chapter contains thermostat level configuration and equipment level configuration procedures. Only the Installer has access to these configuration screens. Related topics Configuration screen Basic configuration Equipment configuration I/O terminal assignment Sensors System switch Discharge air control Dehumidification Valve cycle Advanced configuration Setpoint options - All equipment types Heat pump Cooling options - For Heat pump & Conventional equipment Cooling options - For Fan coil equipment Heating options - For Heat and Conventional equipment Heating options - For Fan coil equipment Pipe sensor thresholds Valve purge Compressor delay time To configure compressor delay time Service mode Standby action Security log

    Page 44

    44 Configuration screen

    4 - Configuration

    Diagnostics Connection User management User roles Home screen (Display management) Display settings Reset to default System status Setpoints System mode Fan speed Configuration screen The configuration screen displays all the configuration items of the thermostat and equipment.
  • Swipe left from the Home screen.
  • On the Quick access screen, tap the configuration
  • button. The Configuration screen appears.

    Page 45

    Basic configuration 45

    Basic Configuration

    Figure 20 Configuration screen Basic configuration The Basic Configuration includes options to configure the thermostat setting such as Device Name, Date and Time, Screen Cleaning, Override Setting, and Service Info. You might have configured these configurations while setting up the thermostat. However, you can change the configuration here again.

    Page 46

    46 Basic configuration

    4 - Configuration

    Figure 21 Basic configuration The following features are covered under the Basic configuration. To rename the device name To configure Date & Time To enable screen cleaning mode To configure override setting To configure Default fan mode To modify service info To rename the device name
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Basic > Device Name. The Device name screen appears. Figure 22 Naming the thermostat

    Page 47

    Basic configuration 47

    Basic Configuration

  • Tap on the text field
  • A keyboard will be displayed on the screen to enter the device name.
  • Enter the device name.
  • Assign a unique name to a thermostat specifying a name to the location where the thermostat is installed. It assists the user to easily identify the device during remote operation of the thermostat.
  • Tap the back button to navigate back to the previous screen and save the settings.
  • To configure Date & Time The date and time of the thermostat is to be set manually. You can configure the Date & time and Daylight savings.
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Basic > Date and Time. The Date & Time screen appears. Figure 23 Date & Time
  • Tap the date to set today’s date.
  • Slide the Display toggle button to the right to set the 24h time format if required.
  • Enable Daylight Savings if required.
  • If Daylight savings is enabled, set the start and end date schedules for daylight savings.
  • Tap the back button to navigate back to the previous screen.
  • To enable screen cleaning mode Screen cleaning mode lock/disable the touch sensitivity of the display for 30 seconds so you clean the device display while the thermostat is functional.
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Basic > scroll down > Screen Cleaning. The Screen Cleaning screen appears.

    Page 48

    48 Basic configuration

    4 - Configuration

    Figure 24 Screen cleaning
  • Tap OK to enable the screen cleaning mode for 30 seconds or tap the back button to
  • navigate back to the previous screen. To configure override setting This settings allow users to manually adjust the system's operation mode, overriding the automatic controls. There are two types of override settings available. Permanent Override - This setting maintains a fixed setpoint 24/7, overriding any scheduled occupied or standby periods. Temporary Override - This allows authorized user to adjust setpoint or operating mode for fixed interval that deviates from standard schedule. The override is activated when the user manually changes the setpoint on the thermostat, switching from the current mode (Occupied/Unoccupied/Standby) to a temporary mode.
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Basic > scroll down > Override Setting. The Override Setting screen appears. Figure 25 Override setting
  • Tap Temporary Override to override the current operational mode for a given period of
  • time. By default, overrides are set to Temporary Override. The Temporary override screen appears.

    Page 49

    Basic configuration 49

    Basic Configuration

    Figure 26 Temporary override
  • Set the time limit that temporary override should last. After this time, setpoint return to
  • the scheduled mode.
  • To make the override permanent, set the override settings as Permanent override.
  • To configure Default fan mode The default fan mode determines the cyclical operating mode of the fan and whether or not it is used for ventilation.
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Basic > scroll down > Default fan mode. The Default Fan Mode screen appears.

    Page 50

    50 Basic configuration

    4 - Configuration

    Figure 27 Default fan mode Auto - It means Fan will be On during Heating / Cooling, and Off when room reaches setpoint. Circulate - If Circulate is available, the fan will run approximately 35% of the time, roughly 20 minutes each hour. Continuous - It means Fan will be On in Occupied mode, and Auto in other modes. In unoccupied/standby, mode will be Auto. Table 17: Default fan mode Default fan mode Fan set on home screen Schedule status Fan behavior Auto Circulate Occupied, Standby (treat as occupied) When there is a demand for heating or cooling, the fan will automatically activate. In the absence of such a demand, the fan will continue to operate in circulation mode to maintain air quality and comfort. Unoccupied, standby (treat as unoccupied) The fan will automatically switch to Auto mode, and the fan settings cannot be adjusted from the home screen. Auto Occupied, Standby (treat as occupied) The fan will remain on when there is a demand for heating or cooling. If there is no such demand, the fan will turn off to conserve energy. Unoccupied, standby (treat as unoccupied) Manual (Low/ high) Occupied, Standby (treat as occupied) The fan will operate continuously based on the selection made in the user manual. Unoccupied, standby (treat as unoccupied) The fan will automatically switch to Auto mode, and the fan settings cannot be adjusted from the home screen.

    Page 51

    Basic configuration 51

    Basic Configuration

    Circulate Circulate Occupied, Standby (treat as occupied) When there is a demand for heating or cooling, the fan will automatically activate. In the absence of such a demand, the fan will continue to operate in circulation mode to maintain air quality and comfort. Unoccupied, standby (treat as unoccupied) The fan will automatically switch to Auto mode, and the fan settings cannot be adjusted from the home screen. Auto Occupied, Standby (treat as occupied) When there is a demand for heating or cooling, the fan will automatically activate. In the absence of such a demand, the fan will continue to operate in circulation mode to maintain air quality and comfort. Unoccupied, standby (treat as unoccupied) The fan will remain on when there is a demand for heating or cooling. If there is no such demand, the fan will turn off to conserve energy. Manual (Low/ high) Occupied, Standby (treat as occupied) The fan should remain operational at all times, as per the user's manual selection. Unoccupied, standby (treat as unoccupied) The fan will automatically switch to Auto mode, and the fan settings cannot be adjusted from the home screen. Continuous Circulate Occupied, Standby (treat as occupied) Circulate button will be disabled. Unoccupied, standby (treat as unoccupied) Auto Occupied, Standby (treat as occupied) If there is a demand for heating or cooling, the fan will be on. If there is no such demand, the fan will remain on at the ventilation speed selected by the user. Unoccupied, standby (treat as unoccupied) If have heating/cooling demand, fan is on. If no heating/cooling demand, fan will be off. Manual (Low/ high) Occupied, Standby (treat as occupied) The fan should remain operational at all times, as per the user's manual selection. Unoccupied, standby (treat as unoccupied) The fan will automatically switch to Auto mode, and the fan settings cannot be adjusted from the home screen. Table 17: Default fan mode (Continued) Default fan mode Fan set on home screen Schedule status Fan behavior

    Page 52

    52 Equipment configuration

    4 - Configuration

    To modify service info Service info contains the maintenance/installer/contractor personnel who provides the periodic maintenance service. To add/modify the details, follow the procedure given below.
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Basic > scroll down > Service Info. The Service info screen appears. Figure 28 Service information
  • Update the name and phone number of the service personnel.
  • Tap the back button to navigate back to the previous screen and save the modified
  • information. Equipment configuration The equipment tab provides options to configure the equipment and devices connected to the thermostat. It also provides options control advanced settings like Discharge air control, Dehumidification, Cooling, Heating, System switch, and Sylk devices settings. To access Equipment screen
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment. The Equipment screen appears.

    Page 53

    Equipment configuration 53

    Equipment Configuration

    Figure 29 Equipment screen To configure equipment and I/O
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Equipment & I/O. The Equipment screen appears. Figure 30 Equipment and I/O

    Page 54

    54 Equipment configuration

    4 - Configuration

  • Tap Equipment.
  • The Equipment page appears. It provides options to select type of equipment such as Fan coil Conventional Heat pump Figure 31 Equipment type Note: The desire option may be “grayed-out” whenever there are insufficient outputs to support this function. Verify I/O is configured appropriately. So the Aux Heat, Dehumidifier, and Humidifier checkboxes available based on the equipment type selection.
  • Tap Equipment Type.
  • The Equipment type page appears. Figure 32 Equipment type selection

    Page 55

    Equipment configuration 55

    Equipment Configuration

    Fan coil Note: The fan coil equipment does not support humidifier/dehumidifier.
  • Tap Fan Coil.
  • The Fan Coil page appears. Figure 33 Fan coil selection 4-Pipe Dual Coil
  • Tap 4-Pipe Dual Coil.
  • The 4-Pipe Dual Coil screen appears. Table 18: 4-Pipe dual coil Valve type Valve operation Options Sub options Description Cooling Valve On/Off Normally closed Set Valve output type as N.C Normally Open Set Valve output type as N.O Floating • Set the output type as Direct or Reverse • Set Valve run time • Set Min position when enabled • Enable sync at mid night Modulating Control Modulating control • Set min output when enabled. • Use Stage 1 cool as enable. Setting Modulating setting • Set output type Direct or Reverse • Set Min output of Modulating valve • Set Max output of Modulating valve

    Page 56

    56 Equipment configuration

    4 - Configuration

    Heating Valve On/Off Normally closed Set Valve output type as N.C Normally Open Set Valve output type as N.O Floating • Set output type as Direct or Reverse • Set Valve run time • Set Min position when enabled • Enable sync at mid night Modulating Control Modulating control • Set min output when enabled. • Use Stage 1 heat as enable. Setting Modulating setting • Set output type Direct or Reverse • Set Min output of Modulating valve • Set Max output of Modulating valve Table 18: 4-Pipe dual coil Valve type Valve operation Options Sub options Description

    Page 57

    Equipment configuration 57

    Equipment Configuration

    4-Pipe Single Coil
  • Tap 4-Pipe Single Coil.
  • The 4-Pipe Single Coil screen appears. Note: If Output is set to 0-10 Vdc
  • Heating Rage: 0.0-4.7 Vdc
  • Cooling Range: 5.3-10.0 Vdc
  • Off voltage is 4.7-5.3Vdc
  • Table 19: 4-Pipe single coil Valve type Valve operation/ Output Options Description Regulating and changeover On/Off Normally open Set Valve output type as N.C Normally close Set Valve output type as N.O Floating
  • Set output type Direct or Reverse • Set output type Direct or Reverse • Set Min position when enabled • Enable sync at mid night Modulating Modulating control • Min output when enabled • Use Stage 1 cool as enabled Modulating setting • Set output type Direct or Reverse • Set Min output of Modulating valve • Set Max output of Modulating valve Changeover Energize on heat
  • Set Changeover relay type
  • Energize on cool
  • Set Changeover relay type
  • 6-Way Valve

    2-10V

    Cooling Range • Configure Min Output for Cooling • Configure Max Output for Cooling • Tap the Info icon to view the minimum allowed deadband range Heating Range • Configure Min Output for Heating • Configure Max Output for Heating Reverse Exchange the heating range and cooling range

    0-10V

    Cooling Range • Configure Min Output for Cooling • Configure Max Output for Cooling • Tap the Info icon to view the minimum allowed deadband range Heating Range • Configure Min Output for Heating • Configure Max Output for Heating Reverse Exchange the heating range and cooling range

    Page 58

    58 Equipment configuration

    4 - Configuration

    If Output is set to 2-10 Vdc
  • Heating Rage: 2.0-5.7 Vdc
  • Cooling Range: 6.3-10.0 Vdc
  • Off voltage is 6.0 Vdc
  • 2-Pipe Single Coil
  • Tap 2-Pipe Single Coil.
  • The 2-Pipe Single Coil screen appears. Table 20: 2-Pipe single coil Heating/Cooling type Controls Options Description Changeover Pipe sensor Set the pipe sensor as input value for changeover method. Network Input Set the network input as input value for changeover method. Changeover Switch Set the digital input as input value for changeover method. Manual Heat & Cool On/Off Normally closed • Set Valve output type as N.C Normally open • Set Valve output type as N.O Floating • Set output type Direct or Reverse • Set Valve run time • Set Min position when enabled • Enable sync at mid night Modulating Control • Set min output when enabled • Use Stage 1 as enable Setting • Set output type Direct or Reverse • Set Min output of Modulating valve • Set Max output of Modulating valve Heat only On/Off Normally closed • Set Valve output type as N.C Normally open • Set Valve output type as N.O Floating • Set output type Direct or Reverse • Set Valve run time • Set Min position when enabled • Enable sync at mid night Modulating Control • Set min output when enabled • Use Stage 1 heat as enable Setting • Set output type Direct or Reverse • Set Min output of Modulating valve • Set Max output of Modulating valve

    Page 59

    Equipment configuration 59

    Equipment Configuration

    Conventional
  • Tap Equipment Type > Conventional.
  • The Conventional page appears. Figure 34 Equipment type - Conventional
  • Select an option for conventional equipment.
  • Heat pump Note: If the Heat pump source is water then set up the Proof of waterflow sensors. See Sensors.
  • Tap Equipment Type > Heat Pump.
  • The Heat Pump page appears. Cool only On/Off Normally closed • Set Valve output type as N.C Normally open • Set Valve output type as N.O Floating • Set output type Direct or Reverse • Set Valve run time • Set Min position when enabled • Enable sync at mid night Modulating Control • Set min output when enabled • Use Stage 1 cool as enable Setting • Set output type Direct or Reverse • Set Min output of Modulating valve • Set Max output of Modulating valve Table 20: 2-Pipe single coil Heating/Cooling type Controls Options Description

    Page 60

    60 Equipment configuration

    4 - Configuration

    Figure 35 Equipment type - Heat Pump
  • Select a source for heat pump. If the source is water, then select the water flow valve
  • position. Fan type Note: The options for fan type varies depending on the equipment selection.
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Equipment & I/O > Equipment > Fan Type. The Fan Type screen appears.

    Page 61

    Equipment configuration 61

    Equipment Configuration

    Figure 36 Fan type - Conventional/Heat pump
  • Select a fan speed.
  • If the fan type is two speed and equipment is conventional.
  • Figure 37 Fan type - Two speed - Conventional equipment
  • If the fan type is two speed and equipment is Heat pump.
  • Page 62

    62 Equipment configuration

    4 - Configuration

    Figure 38 Fan type - Two speed - Heat pump equipment Sensors
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Equipment & I/O > Equipment > Sensors. The Sensors screen appears. Table 21: Fan type - Two speed - Conventional equipment/ Heat pump equipment Parameters Description One Output at a Time One Output at a Time will energized the digital output assigned to current fan speed. Digital outputs assigned to other fan speed will be deenergized. Example:If fan is currently high speed, only High Speed Fan output will be active. Multiple Outputs at a Time Multiple Outputs at a Time will energize the digital output for the current fan speed and keep the lower speed digital outputs energized. Example: If fan is high speed, both High Speed Fan and Low Speed Fan outputs will be active. Ventilation Speed When an operation mode is active (e.g. VentMode), the speed selected for that mode is used to command the Fan Speed Output. Single Heat Stage Single Cool Stage

    Page 63

    Equipment configuration 63

    Equipment Configuration

    Figure 39 Sensors
  • Tap the required sensor, relevant sub menu appears to select the settings.
  • Note: The desire option may be “grayed-out” whenever there are insufficient outputs to support this function. Verify I/O is configured appropriately. To configure Auxiliary heat
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Equipment & I/O > Equipment > select Auxiliary Heat. The Mode screen appears.

    Page 64

    64 Equipment configuration

    4 - Configuration

    Figure 40 Mode screen
  • Set the Peripheral and Supplemental values.
  • Peripheral heat runs in conjunction with main fan heat cycle for improved comfort and is performed by external radiant or other heating resources. Supplemental heat is a form of staged heating that is only initiated when primary fan coil heat function cannot maintain heating setpoint. It is also used in 2-pipe systems for heating whenever system mode is restricted to cooling only based on water temperature. To configure Dehumidifier
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Equipment & I/O > Equipment > select Dehumidifier. The Dehumidifier page appears. Figure 41 Dehumidifer To configure Humidifier
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Equipment & I/O > Equipment > select Dehumidifier. The Humidifier page appears.

    Page 65

    I/O terminal assignment 65

    I/O Terminal Assignment

    Figure 42 Humidifier I/O terminal assignment After connecting the thermostat to equipment, you must configure certain terminals in the thermostat so it can identify the correct purpose and apply the appropriate control schemes. The Configurable I/O tab provides options configure thermostat to the equipment and sensors wired to it. For more information on terminal assignments, refer to Terminal assignment section.
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Equipment & I/O > I/O Assignment The I/O Assignment screen appears.

    Page 66

    66 I/O terminal assignment

    4 - Configuration

    Figure 43 I/O Assignment Note: The options available on the above screen varies based on the configured equipment.
  • Tap the plus button to assign the terminals.
  • Figure 44 Terminals

    Page 67

    I/O terminal assignment 67

    I/O Terminal Assignment

    • Based on selected equipment function the terminals will be pre-assigned. To override default terminal assignment select alternate(s) as required. • If a terminal is assigned incorrect, then there will be a red box around the terminal button. Reassign the terminal. Figure 45 Incorrect terminal assignment • If the same terminal is assigned to two different functions, the user must resolve the conflict by reassigning the terminal. • In the below example, user tried to assign UIO1 to Medium speed fan. But the terminal is already assigned to Drain pan sensor. To resolve this issue, tap the Resolve Conflict button. It opens the Drain pan sensor screen. Reassign the terminal for Drain pan sensor
  • Tap the back button after assigning the terminals.
  • If the user tap the back button without modifying the terminal assignment then the following confirmation message appears. Figure 46 Discard message
  • Tap YES or DISCARD as per the requirement.
  • A confirmation message appears, tap YES to confirm.
  • Page 68

    68 Sensors

    4 - Configuration

    Figure 47 Typical IO assignment for equipment Sensors Thermostat supports Sylk sensors and Control sensors (temperature and humidity only). In order to ensure proper operation and control, configure for Sylk devices only when using Honeywell compatible sensors. To configure sensors
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Sensor Settings. The Sensor Settings screen appears. Figure 48 Sensor settings

    Page 69

    Sensors 69

    Sensors

  • Tap Sensors.
  • The Sensors screen appears. Figure 49 Sensors screen
  • Scroll down to see more sensors.
  • Tap the required sensor, relevant sub menu appears to select the settings.
  • Note: The desire option may be “grayed-out” whenever there are insufficient outputs to support this function. Verify I/O is configured appropriately. To configure Sylk sensors Make sure that the required Sylk devices are connected to the thermostat.
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Sensor Settings > Sylk Sensors. A list of Sylk devices appear with the respective bus address corresponding to the address number listed in the thermostat listing.

    Page 70

    70 Sensors

    4 - Configuration

    Figure 50 Sylk devices Note: The total number of Sylk Devices is restricted by Power and Communication bandwidth. In general, the number of Sylk devices cannot exceed the allowed limit. Contact the Honeywell Technical Support team for additional support.
  • Tap the right arrow in the menu option to view the dip switch bus address setting guide.
  • Table 22: Sylk device dip switches Sylk Address Device Type Sensors DIP Switches 2 Sylk Temperature & Humidity & CO2 sensor

    Tr40

    Tr40-H

    Tr40-Co2

    Tr40-H-

    Co2

    Tr50-3N

    Tr50-3D

    Note: Set the red colored switches to the position as shown in the above image

    Page 71

    Sensors 71

    Sensors

  • Turn on the sensors.
  • To configure Sensor offset
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Sensor Settings > Sensor Offset. The Sensor Offset screen appears. Figure 51 Sensor offset
  • Set the offsets for internal temperature sensor and internal humidity sensor.
  • 3 Sylk Temperature sensor

    Tr40

    4 Sylk Temperature sensor

    Tr40

    5 Sylk Temperature sensor

    Tr40

    8 Outdoor Air Sensor

    C7400S

    10 Discharge Air Sensor

    C7400S

    Table 22: Sylk device dip switches Sylk Address Device Type Sensors DIP Switches

    Page 72

    72 Sensors

    4 - Configuration

    Figure 52 Offset screens for temperature and humidity Note: These offsets should be used only when measured temperature or humidity is verified with calibrated sensor located in same location.

    Page 73

    System switch 73

    System Switch

    To configure Control sensors The thermostat groups the control sensors into three types. There are Local sensor, Remote sensor, and Multi sensor. Local Sensor: Internal TC300B temperature sensor. Installer can configure offsets to on-board temperature and humidity sensors, if desired. Remote Sensor: Space temperature sensor connected to UI/UIO terminal, or TR40 sensor configured at address 2. Multi Sensor: Local Sensor and Sylk sensors at address 2, 3, 4, 5 used together to calculate space temperature.
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Sensor Settings > Control Sensors. The Control sensors screen appears. By default, it shows Local Sensors. If Remote Sensors are also configured then Multi-Sensors and Remote Sensors also appear. Figure 53 Control sensors Note: If the relevant sensors not available then it will be grayed out. System switch To configure system switch
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > System Switch. The System switch screen appears.

    Page 74

    74 Discharge air control

    4 - Configuration

    Figure 54 System switch
  • Select a system switch that corresponds with the HVAC equipment. Commands from the
  • network to control the system switch mode take precedence over the setting on the TC300B. The system switch setting is saved during power outages. Discharge air control The discharge air controller option is available only if the selected equipment type is Fan coil with the floating, modulating valve, or 6-way valves. Enabling Discharge Air Temperature control will result in the thermostat regulating the floating or modulating valves to maintain discharge air temperatures (DAT) within the programmed heating or cooling limits. The discharge air temperature will automatically increase or decrease in proportion to heating or cooling demand. During active cooling event the DAT will modulate between current cooling minus Cooling Initial Offset (default 0°F/C). Increasing cooling demand will decrease DAT until the minimum DAT setpoint is reached and then fan speed will gradually increase until maximum fan speed is reached. Cooling valves will be regulated to attempt to maintain minimum cooling DAT setpoint. Sequence for heating is the same as cooling except initial DAT heating setpoint is setpoint plus Heating Initial Offset (default 0°F/C).

    Page 75

    Discharge air control 75

    Discharge Air Control

    To configure Discharge air control
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Discharge Air Control. The Discharge Air Control screen appears.
  • Enable the Discharge Air Control.
  • Figure 55 Discharge air control
  • Tap Setpoints to set the Maximum Heating, Heating Initial Offset, Maximum Cooling,
  • and Cooling Initial Offset.
  • Tap Heating Gains to set Throttling Range and Heating Integral Time.
  • Tap Cooling Gains to set Throttling Range and Cooling Integral Time.
  • Page 76

    76 Discharge air control

    4 - Configuration

    Figure 56 Discharge air control setpoints
  • Tap the help icon to see the on-screen help.
  • Figure 57 On-screen help

    Page 77

    Dehumidification 77

    Dehumidification

    Dehumidification Dehumidification function will maintain humidity below programmed setpoint using onboard humidity sensor. For systems without reheat the dehumidification function will allow cooling below the target setpoint based on programmed over cool offset. If humidity threshold cannot be achieved once lower space temperature threshold has been reached the dehumidification function will be suspended. For applications with reheat function setpoint will be maintained during dehumidification cycle by activating reheat using heating coil or via auxiliary heat (electric heat). To configure dehumidification
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Equipment > Dehumidification. The Dehumidification screen appears. Enable the dehumidification Figure 58 Dehumidification Note: The Reheat option is applicable only for 4-pipe dual coil. Aux Heat for Reheat is applicable for both 4- pipe single coil and 2-pipe single coil.
  • The dehumidification icon appears on Home screen.
  • Valve cycle Valve Cycle function is used to periodically cycle valve every 24 hours to minimize risk of sticking/binding. To configure valve cycle
  • Swipe left from the Home screen.
  • Page 78

    78 Advanced configuration

    4 - Configuration

  • On the Quick access screen, tap
  • > Equipment > Valve Cycle. The Valve Cycle screen appears. Figure 59 Valve cycle Advanced configuration The Advanced configuration screen displays all the advanced options of the thermostat. To view Advanced options
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Advanced. The Advanced configuration screen appears.

    Page 79

    Setpoint options - All equipment types 79

    Setpoint Options - All Equipment Types

    Figure 60 Advanced configuration - Equipment - Heat pump Note: The second option on the above screen changes as per equipment selected in the Equipment configuration. Also, the Cooling and the Heating tabs menus changes as per the equipment selection. See Equipment configuration. Setpoint options - All equipment types This option allows users to set the maximum or minimum temperature setpoints. To configure setpoint options
  • Swipe left from the Home screen.
  • Page 80

    80 Setpoint options - All equipment types

    4 - Configuration

  • On the Quick access screen, tap
  • > Advanced > Setpoint Options. The Setpoint options screen appears. Figure 61 Setpoint options Table 23: Setpoint options Operation Configuration Type Range Description Stops Cooling Min. Setpoint 50-99°F (Default

    50°F)

    The minimum cool setpoint that can be set by the user Heating Max. Setpoint 40-105°F (Default

    90°F)

    The maximum heat setpoint can be set by the user Limits Thermostat Deadband 2°F-8°F(Default: 3°F) Ensures that the heat setpoint and the cool setpoint maintain a differential minimum temperature span when the thermostat is in auto mode. Temporary Setpoint Limit 0°F - 45°F (Default

    30°F)

    The range above or below occupied setpoint by which the temperature may be altered by user from programmed scheduled setpoint in occupied state or when initiating temporary override of schedule. This includes scheduled occupancy or override of the scheduled occupancy (bypass override). During unoccupied and standby periods, the effective setpoint offset is set to 0 Δ°F. If an occupant wants to change the temporary setpoint, the occupant must first override the schedule to occupied and then the thermostat will allow the occupant to change the temporary setpoint

    Page 81

    Heat pump 81

    Heat Pump

    Heat pump Note: This option is available only when the equipment is configured as Heat pump. See Equipment configuration. To configure Heat pump
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Advanced > Heat Pump. The Heat Pump screen appears. Cooling Recovery Setpoint Ramp 0 -20°F/hr (Default 6°F/hr When outside air temperature is available, the effective cool ramp rate is changed as the outdoor air temperature changes. When the outdoor air temperature is at the minimum cool ramp rate temperature (e.g. 90°F) and above, the effective cool ramp rate is at the minimum cool ramp (e.g. 2 Δ°F/hr). When the outdoor air temperature falls, the cool ramp rate is lowered until the maximum cool ramp temperature (e.g. 70°F) is reached or above, the effective cool ramp is at the maximum cool ramp rate (e.g. 6 Δ°F/hr). Heating Recovery Setpoint Ramp 0 -36°F/hr (Default 8°F/hr When outside air temperature is available, the effective heat ramp rate is changed as the outdoor air temperature changes. When the outdoor air temperature is at the minimum heat ramp rate temperature (e.g. 0°F) and below, the effect heat ramp rate is at the minimum heat ramp (e.g. 2 Δ°F/hr). When the outdoor air temperature is at the maximum heat ramp temperature (e.g. 60°F) and above, the effective heat ramp is at the maximum heat ramp rate (e.g. 8 Δ°F/ hr). Table 23: Setpoint options Operation Configuration Type Range Description

    Page 82

    82 Cooling options - For Heat pump & Conventional equipment

    4 - Configuration

    Figure 62 Heat pump Cooling options - For Heat pump & Conventional equipment To configure cooling options
  • Swipe left from the Home screen.
  • Table 24: Cooling options Type Configuration Type Range Description Lockouts (only for air source heat pump) Compressor Lockout 0 to 70°F (Default 30°F) During heating mode, when the outside air temperature is below the Heat Pump Compressor Lockout setpoint, the compressor stages are disabled and the auxiliary heating is allowed to run. Auxiliary Heat Lockout 30 to 120°F (Default 65°F) During heating mode, when the outside air temperature is above the Heat Pump Aux Heat Lockout setpoint, the auxiliary stages will be disabled. However, if the compressors are locked out by outside air temperature or the unit is commanded to emergency heat mode, the auxiliary heat stages are allowed to run. Auxiliary Heat Aux Heat Ramp Factor 0 to 100 (Default 2) Ramp is used when the thermostat is recovering from the unoccupied setpoint. To avoid the auxiliary heat stages from being used during this period, the user can specify an auxiliary heat ramp factor. This creates a second recovery ramp setpoint for the auxiliary heat. If the heat compressors cannot maintain its recovery ramp or are locked out when the outside air temperature is low, the auxiliary heat ramp will be used to allow auxiliary heat to recover before the occupied period. Enable Aux Heat Delay Aux Heat Delay 30 to 960 minutes (Default 30 min) This timer starts when the highest stage of the previous heating equipment type turns on. Aux Heat will be used (if needed) when the timer expires.

    Page 83

    Cooling options - For Heat pump & Conventional equipment 83

    Cooling Options - For Heat Pump & Conventional Equipment

  • On the Quick access screen, tap
  • > Advanced > Cooling. The Cooling Options screen appears. Figure 63 Cooling options-For Heat pump & Conventional equipment Table 25: Cooling options-For Heat pump & Conventional equipment Cooling type Configuration Type Range Description Lockouts DAT Cooling Low Limit -40 to 60°F (Default 45°F) When the discharge air temperature is below the discharge air low limit setpoint, the cooling control will turn off stages of cool until the discharge air temperature rises above it’s setpoint plus a 2 °F differential. OAT Cooling Lockout -40 to 120°F (Default 35°F) When the outside air temperature is below the cooling lockout setpoint, the cooling control will be disabled. When the outside air temperature is above the cooling lockout setpoint plus 2 °F differential, the cooling control is enabled. Gains Throttling Range 0 to 30°F (Default 4°F) The throttling range is the amount of change in the sensed temperature required to drive the output from 0 to 100%. The throttling range must be narrow enough to provide good control without becoming unstable. The throttling range is determined by factors including: the control application, heating or cooling capacity of the equipment relative to the physical size of the space being controlled, and the control algorithm being used. The narrower (smaller) the throttling range, the more precise the control and the wider (larger) the throttling range, the more stable the control. The objective is setting the throttling range to achieve the optimum balance between precision and stability. Cooling Integral Time 0 to 5000 Sec (Default 2500 Sec) The amount of time the error has continued uncorrected. Integral action corrects the temperature control errors of proportional-only control, but it is slower to react to large temperature or setpoint changes.

    Page 84

    84 Cooling options - For Fan coil equipment

    4 - Configuration

    Cooling options - For Fan coil equipment To configure cooling options
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Advanced > Cooling. The Cooling Options screen appears. Figure 64 Cooling options-For Fan coil equipment Fan Delay Fan Off Delay Time 0-180 Sec Fan run on time after all cooling outputs are turned off. May be used to run fan after all cooling outputs have turned off so that the cooling coil can warm up before the fan turns off to prevent condensation from evaporating into the space. Table 25: Cooling options-For Heat pump & Conventional equipment Cooling type Configuration Type Range Description Table 26: Cooling options-For Fan coil equipment Cooling type Configuration Type Range Description DAT Limit DAT Cooling Low Limit -40 to 60°F (Default 45°F) When the discharge air temperature is below the discharge air low limit setpoint, the cooling control will turn off cooling physical output until the discharge air temperature rises above it's setpoint +2 °F differential.

    Page 85

    Heating options - For Heat and Conventional equipment 85

    Heating Options - For Heat And Conventional Equipment

    Heating options - For Heat and Conventional equipment To configure cooling options
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Advanced > Heating. The Heating Options screen appears. Figure 65 Heating options - For Fan coil equipment Gains Throttling Range 0 to 30°F (Default 10°F) The throttling range is the amount of change in the sensed temperature required to drive the output from 0 to 100%. The throttling range must be narrow enough to provide good control without becoming unstable. The throttling range is determined by factors including: the control application, heating or cooling capacity of the equipment relative to the physical size of the space being controlled, and the control algorithm being used. The narrower (smaller) the throttling range, the more precise the control and the wider (larger) the throttling range, the more stable the control. The objective is setting the throttling range to achieve the optimum balance between precision and stability. Heating Integral Time/ Cooling Integral Time 0 to 5000 Sec (Default 2500 Sec) The amount of time the error has continued uncorrected. Integral action corrects the temperature control errors of proportional-only control, but it is slower to react to large temperature or setpoint changes. Fan Delay Fan Off Delay Time 0-180 Sec Fan run on time after all cooling outputs are turned off. May be used to run fan after all cooling outputs have turned off so that the cooling coil can warm up before the fan turns off to prevent condensation from evaporating into the space. Table 26: Cooling options-For Fan coil equipment Cooling type Configuration Type Range Description

    Page 86

    86 Heating options - For Fan coil equipment

    4 - Configuration

    Heating options - For Fan coil equipment To configure cooling options
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Advanced > Heating. The Heating Options screen appears. Table 27: Heating options-For Heat pump & Conventional equipment Heating type Configuration Type Range Description Lockouts DAT Heating High Limit 60 to 200°F (Default 150°F) When the discharge air temperature is above the discharge air high limit setpoint, the heating control will turn off stages of heat until the discharge air temperature falls below its setpoint minus a 2 °F differential. This will help prevent the discharge air temperature from getting too hot and avoid tripping limits. OAT Heating Lockout 40 to 120°F (Default 65°F) OAT Heating lockout set points defined as when outside air is above the lockout, it will not allow heating to be enabled. When the outside air temperature is below the heating lockout setpoint less a 2 °F differential, the heating control is enabled. Gains Throttling Range 0 to 30°F (Default 4°F) The throttling range is the amount of change in the sensed temperature required to drive the output from 0 to 100%. The throttling range must be narrow enough to provide good control without becoming unstable. The throttling range is determined by factors including, the control application, the response time of the equipment being controlled, and the control algorithm being used. The narrower (smaller) the throttling range, the more precise the control and the wider (larger) the throttling range, the more stable the control. The objective is setting the throttling range to achieve the optimum balance between precision and stability. Heating Integral Time/ Cooling Integral Time 0 to 5000 Sec (Default 2500 Sec) The amount of time the error has continued uncorrected. Integral action corrects the temperature control errors of proportional-only control, but it is slower to react to large temperature or setpoint changes Fan Delay Fan Off Delay Time 0 to 180 Sec (Default 120 Sec) Fan run on time after all heating outputs are turned off. May be used to run fan after all heating outputs have turned off so that the heat coil can cool down before the fan turns off.

    Page 87

    Heating options - For Fan coil equipment 87

    Heating Options - For Fan Coil Equipment

    Figure 66 Heating options - For Fan coil equipment Table 28: Heating options-For Fan coil equipment Heating type Configuration Type Range Description DAT Limit DAT Heating High Limit -60 to 200°F (Default 150°F) When the discharge air temperature is above the discharge air high limit setpoint, the heating control will turn off heating physical output until the discharge air temperature falls below it's setpoint -2 °F differential. This will help prevent the discharge air temperature from getting too hot and avoid tripping limits. Gains Throttling Range 0 to 30°F (Default 10°F) The throttling range is the amount of change in the sensed temperature required to drive the output from 0 to 100%. The throttling range must be narrow enough to provide good control without becoming unstable. The throttling range is determined by factors including, the control application, the response time of the equipment being controlled, and the control algorithm being used. The narrower (smaller) the throttling range, the more precise the control and the wider (larger) the throttling range, the more stable the control. The objective is setting the throttling range to achieve the optimum balance between precision and stability. Heating Integral Time/ Cooling Integral Time 0 to 5000 Sec (Default 2500 Sec) The amount of time the error has continued uncorrected. Integral action corrects the temperature control errors of proportional-only control, but it is slower to react to large temperature or setpoint changes Fan Delay Fan On Delay Time 0 to 30 Sec (Default 30) Fan on delay time after heating outputs are turned on. May be used to run fan after heating outputs have turned on for some times so that heating coil can warm up. Fan Off Delay Time 0 to 180 Sec (Default 120 Sec) Fan run on time after all heating outputs are turned off. May be used to run fan after all heating outputs have turned off so that the heat coil can cool down before the fan turns off.

    Page 88

    88 Pipe sensor thresholds

    4 - Configuration

    Pipe sensor thresholds This feature is suitable for heating when pipe temperature is above threshold, and suitable for Cooling when pipe temperature is below threshold. To configure Pipe sensor thresholds
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Advanced > Pipe Sensor Thresholds. The Pipe Sensor Thresholds screen appears. Figure 67 Pipe Sensor Thresholds Table 29: Pipe sensor threshold Operation Configuration Type Range Description Heat/Cool Thresholds (Standard) Pipe Sensor Threshold for Heating 70 to 90°F (Default

    80°F)

    When the pipe temperature is above the threshold, it is suitable for heating. Pipe Sensor Threshold for Cooling 45 to 65°F (Default

    60°F)

    When the pipe temperature is below the threshold, it is suitable for cooling.

    Page 89

    Valve purge 89

    Valve Purge

    Valve purge This setting for 2-pipe systems cycles valve to ensure accurate changeover temperature sensor reading if there are infrequent heating or cooling cycles. To configure Valve purge
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Advanced > Valve Purge. The Valve Purge screen appears. Figure 68 Valve purge
  • Set the purge time and interval.
  • Hybrid Control Temp Offset (Heat) 5 to 10°F (Default

    5°F)

    When the pipe temperature is above the space temperature and the hybrid control is enabled, than the offset is suitable for heating. Timeout Timer (Heat) 1 to 4 hours (Default 4 hours) When the configured timer expires, the pipe sensor reading is compared to the threshold setting, if the pipe sensor reading is above the threshold, it will generate water temperature. No heating alarm will be raised. Temp Offset (Cool) -10 to -5°F (Default

    -5°F)

    When the pipe temperature is below the space temperature and the hybrid control is enabled, than the offset is suitable for cooling. Timeout Timer (Cool) 1 to 4 hours (Default 4 hours) When the configured timer expires, the pipe sensor reading is compared to the threshold setting, if the pipe sensor reading is below the threshold, it will generate water temperature. No cooling alarm will be raised. Table 29: Pipe sensor threshold (Continued) Operation Configuration Type Range Description

    Page 90

    90 Compressor delay time

    4 - Configuration

    Compressor delay time For water source heat pump applications the compressor delay time ensures the water valve can be fully opened when controlled by thermostat before activating the compressor heat or cool command. To configure compressor delay time
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Advanced > Compressor Delay Time. The Compressor Delay screen appears. Figure 69 Compressor delay time Miscellaneous To configure miscellaneous
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Advanced > Miscellaneous. The Miscellaneous screen appears. Figure 70 Miscellaneous

    Page 91

    Service mode 91

    Service Mode

  • Power Up Delay Time - The thermostat will perform a delayed after controller power up.
  • User can set 0 to 300 Sec delay. The default is 10 seconds.
  • Force Exit Provisional - After updating the firmware, the device enters a provisional stage
  • for approximately 35 minutes to ensure stable system operation. During this time, it is not possible to perform another firmware upgrade. However, there is an option to force the device to exit the provisional stage, allowing for continuous firmware upgrades. Caution: Exercise caution when using the Force Exit Provisional option at your site. Service mode Service mode disables all control algorithms to perform service of the equipment. It also provides options to test the terminals for intended output by connecting the test equipment to the terminal and run the algorithm manually. To enable service mode
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Advanced > Service Mode. The Service mode YES or NO screen appears, tap YES to enable Service mode. Figure 71 Service mode enabling Based on terminal configuration, the following screen displays different options for manual testing. For example, in below screen, single speed fan, Heating equipments, Cooling floating, and Aux heat equipments are configured. Connect these test equipment to the relevant terminals and test for actual output.

    Page 92

    92 Service mode

    4 - Configuration

    Figure 72 Service mode
  • Connect the relevant equipment to the terminal and test its functionality.
  • For more examples, in below images, typical options for two speed fan, variable fan,
  • modulating heat, 6-way valve to test its functionality. Figure 73 Typical service mode options
  • To exit the service mode, on the service mode screen, tap the back arrow button.
  • A confirmation message appears.

    Page 93

    Standby action 93

    Standby Action

    Figure 74 Service mode exit
  • Tap YES.
  • The service mode will exit and thermostat resume normal function. Standby action The Standby Action refers to which mode setpoints to be used while the thermostat is in Standby mode. You can select either Occupied mode or Unoccupied mode. To set up Standby action
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Advanced > Standby Action. The Standby Action screen appears. Figure 75 Standby action
  • Tap Treat as Occupied or Treat as Unoccupied.
  • Security log The security log contains records of the critical security events such as password change, user role switch, firmware upgrade and so on. To view the security log
  • Swipe left from the Home screen.
  • Page 94

    94 Diagnostics

    4 - Configuration

  • On the Quick access screen, tap
  • > Advanced > Security Log. The Security Log screen appears. Figure 76 Security log Diagnostics The diagnostics information of the thermostat helps to service the device based on the log information. To view the Diagnostics
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Advanced > Diagnostics. The Diagnostics screen appears. Figure 77 Diagnostics
  • Log info - Log info of thermostat like device restart and other exception issues.
  • Memory Usage - Memory usage of the firmware.
  • Application Info - Application info shows DDC runtime.
  • Thermal Info - Thermal information of the connected devices.
  • Page 95

    Connection 95

    Connection

    Connection TC300B supports BACnet MS/TP connection and Modbus connection. Either BACnet MS/TP or Modbus connection can be enabled at a time. To connect thermostat via BACnet MS/TP
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Connection. The Connection screen appears. Figure 78 BACnet MS/TP connection
  • Tap the BACnet MS/TP.
  • The BACnet MS/TP screen appears. Figure 79 BACnet MS/TP
  • Tap BACnet MS/TP and enable it.
  • The BACnet MS/TP range screen appears.

    Page 96

    96 Connection

    4 - Configuration

    Figure 80 BACnet MS/TP
  • The device automatically adapts to the baud rate of the MS/TP network. You can also
  • manually select the Baudrate
  • Enter a unique Device ID for the thermostat. It should be different from other TC300B
  • thermostat.
  • Auto-MAC addressing is enabled by default, Installer can also manually set a unique
  • MAC address for the TC300B. Note: The baud rate can be manually configured only after initial 5 minute delay.
  • To do manual configuration, tap Manual.
  • A text box appears below to enter the manual MAC address.
  • Tap Baud Rate, to select a desired baud rate from the list.
  • Page 97

    Connection 97

    Connection

    Figure 81 Baud Rate
  • Tap the back arrow button to navigate back to BACnet MS/TP setting screen.
  • Tap BACnet MS/TP Setting.
  • The BACnet MS/TP setting screen appears. Figure 82 BACnet MS/TP Setting

    Page 98

    98 Connection

    4 - Configuration

  • Set the desired parameters and tap the back arrow button to navigate back to the
  • connection screen. TC300B will try to adapt to the Baudrate of the MS/TP network in the first 4 minutes after startup or MS/TP is enabled. If no Baudrate could be determined, for example, there is a single device on the network, then TC300B will choose the default Baudrate of 76800. After that, the Installer can manually change it to another value. To connect thermostat via Modbus
  • On the Connection screen, tap Modbus and enable it.
  • The Modbus setting screen appears. Figure 83 Modbus
  • Enter a unique address for the thermostat. It should be different from other TC300B
  • thermostat.
  • Set the Baud Rate, Stopbits, and Parity from the list.
  • Tap the back arrow button to navigate back to the connection screen.
  • Page 99

    User management 99

    User Management

    User management The TC300B supports four kinds of user identities as identified in Table 30 with limited privileges as noted. Except for the Installer role these privileges can be reduced in the user settings menu. Passcode rules All the user accounts are passcode protected. When creating the passcode, follow the passcode rules given below. • Passcode length must be between 4 to 12 characters • Do not use spaces • Do not use the same passcode used for other users (across all user types) • If no passcode is entered for basic or Admin, the thermostat will remain at the highest level of access, installer, and will not require a passcode for access. User roles To configure user management
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > User Management. The User Management screen appears. Table 30: User roles and permissions Visitor Basic User Admin Installer System Mode Override View Alarm Temperature Units Fan Speed Configuration Brightness Schedule Setpoint Basic Configuration Advanced Configuration

    Page 100

    100 User roles

    4 - Configuration

    Figure 84 User management Visitor To view the Visitor user role
  • On the User Management screen, select Visitor.
  • Tap
  • to go to the previous screen. Basic user To manage the Basic User role
  • On the User Management screen, select Basic User, and tap
  • The Basic User screen appears.
  • Set a passcode and user permission. The passcode will be used by the user to access the
  • thermostat. Refer to Passcode rules. Note: The Passcode button appears only if the pass is set for the Basic user. Figure 85 Basic user
  • Tap Permission.
  • The Permission screen appears.

    Page 101

    User roles 101

    User Roles

    Figure 86 Basic user permission.
  • Toggle the undesired Permissions to “Off” position.
  • Admin To manage the Admin role
  • On the User Management screen, select Admin, and tap
  • . The Admin User screen appears.
  • Set a passcode and user permission. The passcode will be used by the Admin user to
  • access the thermostat. Refer to Passcode rules. Figure 87 Admin user
  • Tap Permission.
  • The Permission screen appears.

    Page 102

    102 Home screen (Display management)

    4 - Configuration

    Figure 88 Admin user permission.
  • Toggle the undesired Permissions to “Off” position.
  • Installer To manage the Installer role
  • On the User Management screen, select Installer, and tap
  • .
  • Set or change a Passcode. Refer to Passcode rules.
  • Figure 89 Installer Home screen (Display management) This section explains managing the icons displayed on the Home screen and Ambiance screen of thermostat. It is applicable at the device level so any changes on the display management will be applied to all user accounts. To configure the home screen
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Display Management. The Display Management screen appears.

    Page 103

    Display settings 103

    Display Settings

    Figure 90 Display management All icons are enabled by default. You can turn it off by sliding the toggle button to the left.
  • Tap Branding to select a brand name that will be displayed on the home screen.
  • Scroll down to see more options.
  • Note: The the information icon to view the icon names. Display settings Display settings of the thermostat includes increasing/reducing display brightness and settings to off the display, dim the display, or show only ring when the display is on sleep mode. To manage display settings
  • Swipe left from the Home screen.
  • Figure 91 Quick access screen

    Page 104

    104 Display settings

    4 - Configuration

  • On the Quick access screen, tap
  • The Display Settings screen appears. Figure 92 Display settings

  • Tap Brightness.
  • The Brightness screen appears. Figure 93 Brightness
  • Tap Display and move the slider to right to increase the brightness of the display.
  • Tap Ring and move the slider to the right to increase the brightness of the ring.
  • Navigate back to the Display settings screen to configure Inactive display.
  • Tap Inactive Display.
  • The Inactive Display screen appears. The inactive display is when there is no user action on the display. User either can set the display always on or always off.

    Page 105

    Reset to default 105

    Reset To Default

    Figure 94 Inactive display
  • Tap Display Off to set the display off. However, the ring LED breaths to show the system
  • mode. Or, tap Always On to show both display and ring LED. Or, tap Always Off to keep both ring LED and display off. Reset to default User can reset the entire thermostat to the factory default or reset only temperature setpoints and schedule to factory default. To reset the factory default setting
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Reset to default. The Reset to Default screen appears. Figure 95 Reset to default
  • Tap Reset Weekly Schedule & Setpoint to only reset the temperature and schedule
  • setpoint. It retains other configurations.
  • Tap Reset All to fully reset the thermostat. It deletes all the configurations and user data.
  • Tap Restart Device to restart the device without deleting any data.
  • Page 106

    106 System status

    4 - Configuration

    Figure 96 Weekly reset and confirmation message
  • Upon successful reset, user will be notified by a notification banner.
  • System status The system status shows device information, live status and readings of the sensors that are operated or connected with the thermostat. These values are view only. To view system status
  • Swipe left from the Home screen.
  • Figure 97 Quick access screen
  • On the Quick access screen, tap
  • The System status screen appears.

    Page 107

    Setpoints 107

    Setpoints

    Figure 98 System status Setpoints To configure setpoint settings
  • Swipe left from the Home screen.
  • Table 31: System status Operating status Equipment type, Current operating mode, Heat status, Cool status, Aux heat, Fan status, Indoor temperature, Indoor setpoint, Indoor humidity, Indoor CO2, Discharge air temperature, Discharge air control setpoint, Pipe temperature, Recovery status, Override remaining, Run time, Restart reason, Terminal load, UTC offset Schedule Current schedule time, Current occupancy state, Current schedule state, Next schedule state, Time to next schedule state, Configurable I/O All terminals ON/OFF status. Device Model name, Boot loader version, Firmware version, Application version, UUID, Serial No. Network status For BACnet MS/TP: Device ID, MAC address, Baud rate. For Modbus: Address, Baud rate, Parity, Stopbits Service Service personnel name and phone number.

    Page 108

    108 Setpoints

    4 - Configuration

    Figure 99 Quick access screen
  • On the Quick access screen, tap
  • The Setpoint screen appears. Figure 100 Define the setpoints

  • On the Setpoint screen, tap Occupied, Standby, or Unoccupied
  • The Occupied screen appears. Figure 101 Occupied Tip: Long press the +/- button to quickly increase or decrease the value.

    Page 109

    System mode 109

    System Mode

  • Configure the required setpoint limits for Occupied, Standby, and Unoccupied modes.
  • Thermostat performs limit checking on all temperature setpoints, in case setpoint relationships are violated. • Occupied mode treats the building space as occupied and configured with comfort setpoints. • Unoccupied mode treats the building space as not occupied and configured with energy savings setpoints. • Standby mode setpoints are configured in a way that target setpoint levels can be achieved quickly with the onset of the next occupied period. • Temporary mode allows the user to change the temperature setpoints of the Occupied mode after the user switches to the temporary mode from the Occupied mode. This is not possible in Unoccupied mode and Standby mode. • Minimum cool setpoint and maximum heat setpoint can be adjusted, default minimum cool setpoint is 50°F, maximum heat setpoint is 90°F. Heat setpoint range: 40°F-90°F; Cool setpoint range: 50°F-99°F. • While configuring the temperature range make sure that the unoccupied heat <= standby heat <= occupied heat < occupied cool <= standby cool<= unoccupied cool. • Occupied cool setpoint should be at least a deadband value bigger than occupied heat setpoint. Occupancy sensor behavior • The occupancy sensor only affects the effective occupancy when the scheduled occupancy state is Occupied: • When occupancy sensor state is occupied, the effective occupancy will act as occupied. • When occupancy sensor state is unoccupied, the effective occupancy will change to standby. • When the scheduled occupancy state is unoccupied or standby, the effective occupancy will follow scheduled occupancy state, will ignore the occupancy sensor’s value. System mode To change the system mode
  • On the Home screen, tap mode icon, for example
  • The Mode screen appears. Figure 102 System mode

  • Select a mode and tap the back arrow button.
  • The mode is changed.

    Page 110

    110 Fan speed

    4 - Configuration

    Fan speed To change the fan speed
  • On the Home screen, tap mode icon, for example
  • The Fan Speed screen appears. Figure 103 Fan speed

  • Select a fan speed and tap the back arrow button.
  • The fan speed is changed. Auto fan can be selected only during Standby or Unoccupied status. During dehumidification, the fan speed will be limited to low speed automatically.
  • Tap the help icon to view the fan mode description.
  • Figure 104 Fan speed help

    Page 111

    Chapter

    5 Alarms 111 Alarms This chapter explains alarms and their configuration procedures. Related topics Alarms Alarm notification signs Alarm notification Alarm preference Unacknowledged alarms List of alarms and their severity Managing the alarms Alarms In the TC300B thermostat, alarms are configured for predefined set values. When the values are breached, the alarms are triggered and displayed on the home screen as banner notification, dot notification, and on the Alarm button. You can view the triggered alarms and acknowledge them. Alarm notification signs The alarm menu notification icon has two color codes to indicate the severity of the alarm. The following table describes the available signs with color codes of the alarm screens.

    Page 112

    112 Alarm notification

    5 - Alarms

    Alarm notification The alarms can be configured as banner notification or dot notification as per the alarm configuration. The banner notification is pop-up on the home screen whereas the dot notification appears beside the time. For alarm configuration, refer to Alarm preference. Figure 105 Alarm banner notification You can tap the banner notification to view the alarm and acknowledge it. If multiple alarms are triggered then the latest one (high) will be displayed on the home screen. After tapping the banner, it takes you to the Alarm screen. • High - Red color banner • Medium - Orange color banner Alarm preference To create alarm preference
  • Swipe left from the Home screen.
  • On the Quick access screen, tap
  • > Alarm Preference. The Alarm preference screen appears. Icons Description High Medium

    Page 113

    Alarm preference 113

    Alarm Preference

    Figure 106 Alarm preference
  • Tap Alarm.
  • A list of alarm types appears.

    Page 114

    114 Alarm preference

    5 - Alarms

    Figure 107 Alarm types
  • Tap an alarm type, for example, Proof of air flow alarm.
  • The configuration screen of the alarm type appears.

    Page 115

    Alarm preference 115

    Alarm Preference

    Figure 108 Alarm configuration screen Alarm reason description is displayed on the screen.
  • Toggle the Allow Banner Notification to on to get the banner notification of the this type
  • of alarm on the home screen. Note: Dot notification of alarm is default. The dot will appear on Alarm bell icon on the home screen and Configuration screen.
  • Toggle the follow up actions such primary heating and cooling shutdown, and Aux heat
  • shutdown for this alarm if required. To configure alarm limits
  • On the Alarm Preference screen, tap Alarm Limits.
  • The Alarm Limits screen appears. Figure 109 Alarm limits
  • Tap Space Temperature Limits to set the limits for space temperature, when its break,
  • alarm will be raised.

    Page 116

    116 Unacknowledged alarms

    5 - Alarms

  • Tap Discharge Temperature Limits to set the limits for DAT, when its break, alarm will be
  • raised.
  • Tap Outdoor Air Temperature Limits to set the limits for OAT, when its break, alarm will
  • be raised.
  • Tap Pipe Temperature Limits to set the limits for pipe temperature, when its break,
  • alarm will be raised. Figure 110 Alarm limits Unacknowledged alarms In addition to the banner notification, all other alarms (for which the notification is not configured) can be viewed and acknowledged under the Alarm screen. The Alarm tab displays the alarms that have not been acknowledged by the user. If there are unacknowledged alarms, the Alarm button will have a visual dot notification as per the severity of the alarm. To view the unacknowledged alarms
  • Swipe left from the Home screen.
  • On the Quick access screen, tap the bell (Alarm) icon.
  • Figure 111 Home screen - Alarm Tab The Alarm Preference screen appears.

    Page 117

    Unacknowledged alarms 117

    Unacknowledged Alarms

    Figure 112 Alarm preference - Alarm
  • Tap Alarm.
  • A list of unacknowledged alarms appears. Figure 113 Unacknowledged alarms
  • Tap an Alarm name.
  • The corresponding alarm property screen appears. The alarm property screen describes the nature of event state transition.

    Page 118

    118 List of alarms and their severity

    5 - Alarms

    Figure 114 Alarm detail
  • Tap CONFIRM.
  • The Alarm Detail screen appears. Figure 115 Alarm detail
  • Tap SERVICE to see the service phone number.
  • List of alarms and their severity The list of alarms in the Commercial Connected thermostat is as follows Alarms Severity Proof of Air Flow Alarm High Space Freeze Protection Alarm High Space Temperature Sensor Failure High/Medium Space Temperature Out of Range High/Medium Space Humidity Sensor Failure High/Medium Discharge Air Temp. Sensor Failure High Discharge Air Temperature out of range alarm Medium Drain Pan Sensor Alarm High Sylk Device Communication Failure High Pipe Sensor Failure High

    Page 119

    Managing the alarms 119

    Managing The Alarms

    Managing the alarms Pipe Sensor Out of Range High Water Temperature is Not Suitable for Heating/Cooling High Room Temperature Changing Trend is Reversed with System Mode High Unknown Time Medium Proof of Water Flow Alarm High Alarms Severity

    S.N0

    Alarm Trigger Scenario Action Level 1 Proof of Air Flow Alarm (fan state) An input (e.g., a current switch or differential pressure switch) should be available to monitor proof of air flow in the Fan Coil Unit. When configured, the control system will check this digital input once per second. If the fan is supposed to be on but is not, an alarm should be generated. For example, users can configure a DIO/UIO terminal as a binary input to detect the fan's status. When DIO2 is set as the Fan Command, and the device sets DIO2 to 'on,' if the digital input indicates no air flow for 60 consecutive seconds, a 'Proof of Air Flow' alarm will be triggered. Depending on the alarm configuration:
  • Display Only: An alarm will be
  • generated, and an alarm indicator will be displayed.
  • The control system will shut down
  • both heating and cooling outputs. The fan speed will follow the fan control logic. (1) The fan will remain on if there is still a call for heating or cooling. (2) In other scenarios where the fan should be on, the fan will operate based on the scheduled status: when the fan speed is set to low/ medium/high, it will be on if the schedule status is 'occupied,' 'temporary,' or 'permanent.' If the fan speed is set to 'circulate,' the fan will run for at least 20 minutes per hour.
  • Upon Alarm: Dehumidification
  • will be disabled. Both cooling and heating outputs, as well as the fan, will be turned off. High

    Page 120

    120 Managing the alarms

    5 - Alarms

    2 Proof of water flow alarm An input (e.g., a current switch or pressure switch) should be available to monitor proof of water flow in the heat exchanger loop. When configured, the control system will check this digital input once per second. For example, users can configure a DIO/UIO terminal as a binary input to detect the water flow's status. Set DIO2 as the proof of waterflow sensor, and configure the sensor as Normally Open. When there is a heating/cooling command, and the water flow valve is none or open, if the digital input indicates 'Inactive' ('Active' if Normally Closed Sensor ) for 120 consecutive seconds, a 'Proof of Water Flow' alarm will be triggered. If water flow alarm is detected, compressor will be disabled. depend on the alarm configuration:
  • Display only: It will generate an
  • alarm and alarm indicator is displayed.
  • Interlock stage: The controller
  • shall disable the heat pump compressor and report an alarm. (Thermostat will shut down Compressor after a time delay 120s, and this function is enabled by default.) Auxiliary heat is still available. The fan will continue to operate normally. If still call for heating/cooling, water flow valve still open. High 3 Space Freeze Protection Alarm When the space temperature falls below 42.8°F (6°C) for more than 2 minutes, a frost alarm will be triggered. If the controller is disabled, in test mode, or in any other higher-priority mode defined by the application, the frost alarm will not be activated.
  • If the system mode is set to OFF,
  • the freeze protection feature will activate, utilizing the effective heating setpoint, until the room temperature reaches either the heating setpoint or 8°C (46°F).
  • If the system mode isn't set to
  • OFF, it will operate based on the standard control logic. High 4 Sylk Device Communicatio n Failure If any of the Sylk sensors experience a malfunction, an alarm will be activated. This alarm will provide detailed failure information sourced from Sylk, e.g., addr10: DAT sensor malfunction. In case a sensor malfunctions, the thermostat will deactivate all control functions linked with that sensor, behaving as if that sensor had never been set up. High 5 Discharge Air Temperature sensor failure
  • DAT sensor fault: Open/short limit is
  • detected on Discharge air sensor(DIO1/DIO2/UIO1/UIO2)
  • DAT reading outside of the following
  • range (Range can be set on the Alarm Limits screen): High Limit: default 80°F,70°F to 180°F Low Limit: default 45°F,35°F to 65°F
  • DAT sensor fault: The thermostat
  • will deactivate all control functions related to the failed sensor, meaning it will function as though the sensor wasn't configured.
  • DAT out of range: The thermostat
  • will not deactivate the control function. The user need to check the equipment for correct operation. High (failure)/ Medium (out of range)

    S.N0

    Alarm Trigger Scenario Action Level

    Page 121

    Managing the alarms 121

    Managing The Alarms

    6 Space Temperature Sensor Failure
  • Local Space temp as the main
  • control and sensor fault is detected.
  • Remote Space temp as the main
  • control. sensor fault is detected.
  • Multi space temp as the main control.
  • All/Some of the temp sources have sensor fault detected.
  • There is a network input space
  • temperature, and the network input space temperature value is below -40°F or above 150°F.
  • If the sensor is utilized for the
  • control loop and network input of temperature is available, the thermostat will only trigger an alarm.
  • If the sensor is used for the
  • control loop and the network input of temperature/humidity is not available, the thermostat will turn off all output controls for the Heating and Cooling equipment. The fan will continue to operate normally. High (Action 2)/ Medium (Action 1) 7 Space Temperature out of range alarm The space temperature has exceeded the defined range (you can set this range on the alarm limits screen). This applies to whichever sensor is acting as the space temperature sensor, including network inputs. The thermostat will only trigger an alarm. Medium 8 Space Humidity Sensor Failure
  • The Local Space Humidity sensor is
  • used as the primary data source for control, and a fault has been detected in this sensor.
  • The Remote Space Humidity sensor
  • is used as the primary data source for control, and a fault has been detected in this sensor.
  • Multiple Space Humidity sensors are
  • used as the primary data sources for control, and faults have been detected in one or more of these sensors.
  • If the sensor is utilized for control
  • loops and network input for temperature/humidity is available, the thermostat will only trigger an alarm.
  • If network input for temperature/
  • humidity is not available, the thermostat will disable all control functions (e.g., humidity control for humidification or dehumidification) related to the malfunctioning sensor. High(Action 2)/ Medium(Ac tion 1) 9 Unknown Time The thermostat has been disconnected from power for an extended period, causing the real-time clock (RTC) to reset. Ask the user to update the date and time. Medium 10 Drain pan sensor alarm The user can set up the DIO/UIO terminal as a binary input to monitor water leakage. Upon activation of this input, a drain pan alarm will be initiated. User can configure the operation would be taken when drain pan alarm is detected: 1, disable cooling. 2, disable heating. 3, disable fan High 11 Pipe sensor failure Should a fault be detected with the pipe sensor, or if the temperature of the pipe falls outside the specified range, the system will respond accordingly. Configurable range settings can be adjusted in the 'Alarm Limits' section. High Limit: Default at 180°F (range: 70°F to 220°F). Low Limit: Default at 40°F (range: 30°F to 60°F). Both heating and cooling functions will be deactivated. High

    S.N0

    Alarm Trigger Scenario Action Level

    Page 122

    122 Managing the alarms

    5 - Alarms

    12 Water temperature is not suitable for Heating/ Cooling Applicable only for Dual-Pipe FCU Heating/Cooling Systems.
  • Based on the Pipe Sensor transition
  • mode: a. If Hybrid Control is set to Off: For heating, if the Pipe Sensor reading is below the Pipe Sensor Threshold for Heating, or for cooling, if the Pipe Sensor reading is above the Pipe Sensor Threshold for Cooling. b. If Hybrid Control is set to On: For either heating or cooling, even though the Pipe Sensor reading might be below or above the corresponding Threshold, if it's within 5°F (Temp Offset, configurable) of the space temperature, no alarm is triggered. However, if it remains below or above the respective Threshold for 4 hours (Timeout Timer, configurable), an alarm is triggered.
  • Based on Network Input Changeover
  • Mode: If 'ni_pipetempmode' is opposite to the current heating or cooling mode or is set to 'no use'.
  • Based on Changeover Switch Mode:
  • If the switch is set to heating while the current mode is cooling, or if the switch is set to cooling while the current mode is heating. The heating/cooling valve will be closed, and the fan will run based on the fan speed configuration. While the alarm exists, use a purge interval of 0.5 to perform a pipe purge. High 13 Room temperature changing trend is reversed with system mode
  • If heating is enabled, but there's a
  • drop of ≥1°F within 30 minutes, an alarm will be triggered.
  • If cooling is enabled, but there's an
  • increase of ≥1°F within 30 minutes, an alarm will be triggered. Depend on the alarm configuration:
  • If the toggle button is turned off,
  • only the alarm will be reported.
  • If the toggle button is turned on,
  • both heating and cooling will be deactivated. High

    S.N0

    Alarm Trigger Scenario Action Level

    Page 123

    Chapter

    6 About schedule 123 Scheduling About schedule TC300B enables you to plan operations based on the time of day and holidays. This scheduling structure allows you to control day-to-day operations with the standard schedule. The holiday schedule controls days or times when a facility is typically unoccupied. The event schedule controls periods outside normal occupied times. The holiday schedule overrides the standard schedule and the event schedule overrides the holiday and standard schedules within a schedule set. Schedules use the setpoint configuration of Occupied, Unoccupied, or Standby modes. Occupied mode treats the building space as occupied and configured with comfort setpoints. Unoccupied mode treats the building space as not occupied and configured with energy savings setpoints. Standby mode setpoints are configured in a way that the setpoints can quickly change to the Occupied mode when switched. Standby mode setpoint saves energy higher than occupied mode and lesser than the Unoccupied mode. Temporary mode allows the user to change the temperature setpoints of the Occupied mode after the user switches to the temporary mode from the Occupied mode. This is not possible in Unoccupied mode and Standby mode. When a schedule uses the Occupied mode but the Occupancy sensor reads unoccupied, then the thermostat switches automatically to the Standby mode. In other scenarios, the thermostat follows the schedule status and the occupancy sensor’s value has no impact on it. How schedules works When you set up schedules, it is important to understand the relationship of the schedules in the schedule set and how to use each one. • Standard schedule: Use the weekly schedule to program occupied and standby periods for each of the week. • Holiday schedule: Use holiday schedules to set holidays that “float” or occur on a specific date each year. Up to 10 holidays can be created.

    Page 124

    124 Weekly schedule

    6 - Scheduling

    • Special event: Use Special event to create up to 10 special events. Note: Holiday schedules automatically write a 12:00 AM OFF time, which is in effect unless it is overridden by an event schedule. Related topics Weekly schedule Holiday schedule Special event Weekly schedule To add a new time value to a weekly schedule
  • Swipe left from the Home screen.
  • The Quick access screen appears. Figure 116 Quick access screen
  • On the Quick access screen, tap
  • Schedule. The schedule main screen appears which lists all types of schedules available in the thermostat. Figure 117 Schedule types

    Page 125

    Weekly schedule 125

    Weekly Schedule

  • Tap Weekly to add a new schedule.
  • The Weekly screen appears. Figure 118 Weekly schedule screen
  • Select a day when to apply the weekly schedule.
  • Tap Add new event
  • The Create screen appears. It displays two event types for scheduling. Occupied and Standby. Figure 119 Weekly event screen
  • Tap the information icon to read the schedule events limits.
  • Figure 120 Weekly Schedule help information
  • Set the start and end time for the event.
  • Page 126

    126 Weekly schedule

    6 - Scheduling

  • Tap an event type (Occupied or Standby).
  • Tap SAVE.
  • The Weekly screen appears. It displays the created schedule under Monday. You can copy the schedule to other days. Refer to Copy the schedules from one day to another. Figure 121 Weekly schedule. Note: Scroll horizontally to view the entire screen.
  • To add another schedule, tap Add new event.
  • Tap the back button to exit the scheduling.
  • Note: System would be unoccupied automatically outside the scheduled time slot.

    Page 127

    Weekly schedule 127

    Weekly Schedule

    Edit or delete weekly schedules The existing weekly schedules can be edited from the Weekly schedule screen. To change or delete an existing weekly schedule
  • On the Weekly schedule screen, tap the schedule to be modified.
  • The Edit screen will appear. Figure 122 Editing a regular schedule
  • Select the new Start and End time and mode.
  • Tap SAVE to save changes or Tap DELETE to delete the schedule.
  • Page 128

    128 Weekly schedule

    6 - Scheduling

    Copy the schedules from one day to another The TC300B enables the user to copy an existing regular schedule. To copy a schedule from one day to another
  • Navigate to the Weekly schedule screen from where the schedule is to be copied.
  • Select a day to copy.
  • Tap
  • to copy schedules from Monday. Copy screen will appear. Figure 123 Copy Schedule
  • Tap on the days of the week for which schedule is to be copied.
  • Figure 124 Select Days
  • Tap CONFIRM.
  • Schedule copied successful confirmation message appears.

    Page 129

    Holiday schedule 129

    Holiday Schedule

    Figure 125 Copy successful Holiday schedule Holidays are defined as reoccurring events that are different from the weekly schedule, can be Occupied or Standby, or by default Unoccupied. So the Unoccupied/Standby mode setpoints will be executed on the holidays. There are two holiday types are available to choose. There are Floating date and Specific date. Only one day can be selected for the floating holiday type whereas multiple days can be selected for Specific date type. To schedule a holiday
  • Swipe left from the Home screen.
  • The Quick access screen appears. Figure 126 Quick access screen
  • On the Quick access screen, tap
  • Schedule.

    Page 130

    130 Holiday schedule

    6 - Scheduling

    Figure 127 Schedule types
  • Tap Holiday to add a new holiday schedule.
  • The Holiday screen appears. Figure 128 Holiday screen
  • Tap the add button to add a Holiday.
  • The Create Holiday screen appears. Figure 129 Creating Holiday
  • Tap Date.
  • The Set Date screen appears.

    Page 131

    Holiday schedule 131

    Holiday Schedule

    Figure 130 Set Date
  • Tap Floating Date to schedule a floating date as a holiday (Organization related
  • holidays) or tap Specific Date to schedule festival holidays, government holidays, or public holidays. If Floating date is selected, then you can choose only one day to create an event.
  • Tap the clock icon.
  • Select a date.
  • Tap CONFIRM.
  • The Set Date screen appears. If you are configuring a Specific Date holiday type, then you can add multiple days by tapping the How is the holiday with first date is fixed date.
  • Tap Save.
  • The Create Holiday screen appears.
  • Tap Event to configure the actions to be executed on the configured holiday (s).
  • Tap Set Event.
  • Event list screen for the set date appears. You can add a maximum of four events. Figure 131 Date screen for special events
  • Tap Add new event.
  • The Create screen appears.

    Page 132

    132 Holiday schedule

    6 - Scheduling

    Figure 132 Create holiday vent screen
  • Tap the Start clock icon to set the event start time.
  • Set the start time and then tap CONFIRM.
  • Tap the End clock icon.
  • Set the event end time and then tap CONFIRM.
  • Tap Occupied or Standby based on your requirement.
  • Tap SAVE.
  • The created event appears on the Holiday screen.
  • Tap SAVE.
  • Tap Done.
  • The holiday creation successful message appears.

    Page 133

    Holiday schedule 133

    Holiday Schedule

    Edit or delete Holiday The existing weekly Holidays can be edited from the Holiday screen. To change or delete an existing holiday
  • On the Holiday screen, tap the schedule to be modified.
  • The Edit screen will appear. Figure 133 Editing a regular Holiday
  • Select the new Start and End time and mode.
  • Tap SAVE to save changes or Tap DELETE to delete the schedule.
  • Page 134

    134 Holiday schedule

    6 - Scheduling

    Copy the Holiday events from one day to another The TC300B enables the user to copy an existing holidays. To copy a schedule from one day to another
  • Navigate to the Holiday screen from where the holiday is to be copied.
  • Select a day to copy.
  • Tap
  • to copy holiday from Monday. Copy screen will appear. Figure 134 Copy holiday
  • Tap on the days of the week for which schedule is to be copied.
  • Figure 135 Select Days
  • Tap CONFIRM.
  • Holiday copied successful confirmation message appears.

    Page 135

    Special event 135

    Special Event

    Figure 136 Copy successful Special event Special events are one time events that are different from the weekly schedule. To create a special event
  • Right swipe the home screen.
  • On the Quick access screen, tap Schedule and then tap Special Event.
  • The Special Event screen appears. Figure 137 Special event screen
  • Tap the add button.
  • The Create Special Event screen appears. Date is mandatory to create a special event.

    Page 136

    136 Special event

    6 - Scheduling

    Figure 138 Create special event
  • Tap Date.
  • The Set Date screen appears. Figure 139 Set date screen
  • Select a date.
  • Note: The thermostat supports special event configuration only for three years from the current date. If the special event reoccurs on multiple days, then increase the holiday count.
  • Tap Done.
  • The Create Special Event screen appears.
  • Tap Event.
  • Event list screen for the set date appears. You can add a maximum of four special events for the particular date.

    Page 137

    Special event 137

    Special Event

    Figure 140 Adding new event
  • Tap Add new event.
  • The Create Event screen appears.
  • Tap the clock icon for Start.
  • Set the special event start time and then tap CONFIRM.
  • Tap the clock for End.
  • Set the special event end time and then tap CONFIRM.
  • Tap Occupied or Standby based on your requirement.
  • Tap SAVE.
  • The created special event appears under the special event date screen.
  • Tap Save.
  • Tap Done.
  • You have created a special event. To delete a special event
  • On the special event screen, tap a special event.
  • A confirmation message appears.
  • Tap DELETE.
  • The special event is deleted. Note: Elapsed Special Events will automatically be deleted by the system.

    Page 138

    138 Special event

    6 - Scheduling

    Page 139

    ® U.S. Registered Trademark © 2024 Honeywell International Inc. 31-00644-02 | Rev 05-24 Honeywell | Building Automation 715 Peachtree Street, N.E., Atlanta, GA 30308, United States. Buildings.honeywell.com

    More from Honeywell

    Similar Thermostats